5.2.5 Mounting the detachable conductor bolt (option)
Fig. 12: Mounting the detachable conductor bolt
Item
Part
Item
Part
1
Detachable conductor bolt
2
Suitable lifting equipment
► Screw a pulling rod into the drilled hole on the face side of the detachable conductor bolt.
► Lower the bushing slowly onto the transformer.
► Whilst lowering the detachable conductor bolt slide the detachable conductor bolt into the
bushing with the pulling rod.
► Mount the head armature of the bushing (
on page 32).
Range STARIS®-Sia+