In different connection modes, PMAC770 samples the system frequency from
different channels. In 3-phase 3-wire connection mode, PMAC770 samples the
frequency from line AB voltage channel. In other connection modes, it samples
frequency from phase A voltage channel. In case phase A voltage is failure, it
samples frequency from phase C voltage channel. In case both phase A and C
voltage are failure, it samples from phase B voltage channel.
9.
9.
9.
9.8
8
8
8 Demand
Demand
Demand
Demand calculation
calculation
calculation
calculation
PMAC770 provides demand analysis for three phase current, total active power, total
reactive power and total apparent power.
PMAC770 supports two demand modes: Fixed Block and Rolling Block.
Users can set demand interval as 5min, 10min, 15min, 30min or 60min.
In Fixed Block mode, users do not need to set the subinterval.
In Rolling Block mode, users should set subinterval the subinterval: 1min, 2 min, or 3
min. Show as below sheet:
Optional
Optional
Optional
Optional Intervals
Intervals
Intervals
Intervals (mins)
(mins)
(mins)
(mins)
Programmable
Programmable
Programmable
Programmable Subintervals
Subintervals
Subintervals
Subintervals (mins)
(mins)
(mins)
(mins)
5
1
10
1 or 2
15
1 or 3
30
1, 2, or 3
60
1, 2, or 3