Summary Screen & LCD Setting
Function
Line
Method
Result
Options /
Comments
Summary Display
Lines & dynamic point
setting
SL1…32
SL(x)x=abc…
Assign
Screen Line
text as information or in
relation to SP1…32
Alpha/numeric, 40
characters max.
SP1…32
SP(x)x=nnn
Assign
Screen Point
dynamic point value
Point #
SLL1…32
SLL(x)x=nnn
Assign
Screen Line Logic
point who’s value
>0 will cause the related screen line to appear
at the top of the display (alarm state for
instance)
Point #
SLS1…32 SLS(x)x=1…3
Assign LCD font size & point number format
per line.
Type 0 & 1 are small font. Type 2 & 3 are large
font. 5 digit point format is standard.
8 digit point format would normally be for pulse
counts or other metering related values read in
via NIO
0 = 21 character/5 digit
1 = 16 character/8 digit
2 = 9 character/5 digit
3 = 4 character/8 digit
Manual Override / Release
Values that have been manually set will be indicted in HyperTerminal by an
M
tag next to the displayed
value. The BACnet priority level = 9
Manualled physical inputs (points 1…4 & 17…20) will revert to ‘Auto’ after being Released or after a
power reset. Physical outputs will retain the Manual setting after a power reset if the Manual state is
Written (
W
) before being released, thereby making the Manual state the power-up default state.
Function
Enter
Result
Options /
Comments
Manual a
Digital
Point #=1, 0
Digital on or off
1=On
0=Off
Example: 37=1
Manual an
Analogue
Point #=0…
n
0…100% block output
Block range 0….max
Example: 25=50 (AO1 50% output
/ 5Vdc output)
Release
Manual
overrides back
to ‘Auto’
*
R
R=1…152
Inputs will return to auto state/value.
Other points will remain at manualled
state/value until power reset or
commanded
Example 1: R
All overrides are cleared
Example 2: R=9
DO1 (point 9) only return to Auto