Manual Override / Release
Values that have been manually set will be indicted in HyperTerminal by an
M
tag next to the displayed
value. The BACnet priority level = 9
Manualled physical inputs (points 1…4 & 17…20) will revert to ‘Auto’ after being Released or after a
power reset. Physical outputs will retain the Manual setting after a power reset if the Manual state is
Written (
W
) before being released, thereby making the Manual state the power-up default state.
Function
Enter
Result
Options /
Comments
Manual a
Digital
Object #=1, 0
Digital on or off
1=On
0=Off
Example: 37=1
Manual an
Analogue
Object #=0…
n
0…100% block output
Block range 0….max
Example: 25=50 (AO1 50% output
/ 5Vdc output)
Release
Manual
overrides back
to ‘Auto’
*
R
R=1…193
Inputs will return to auto state/value.
Other points will remain at manualled
state/value until power reset or
commanded
Example 1: R
All overrides are cleared
Example 2: R=9
DO1 (point 9) only return to Auto