6
2. Light c time control (1 to 14): The starting process is the same as pure light control. After operating for a preset period of
time (settable from 1 to 14 hours), the load stops operation automatically.
3. Manual mode (15): In this mode, the user can switch the load on or off by the key, no matter whether it's day or night.
4. Debugging mode (16): In cases of 6V with light signals, the load will be shut off. In cases of 5V (varies according to the preset light
controlled voltage and system voltage) without light signals, the load will be switched on. This mode enables fast check of the
correctness of system installation during installation and debugging.
5. Normal on (17): The energized load keeps in output state.
LED Display
Mode
00
Pure light control mode
01-14
Light c time control (1 to 14 hours)
15
Manual mode
(
default
)
16
Debugging mode
17
Normal on mode
Manually Switching On/Off Load
When the load mode is set to 15 (manual mode), short press the key (non-setting mode) in any interface to switch on or off the
load.
Note: As load start is a type of soft start, display of the load icon on the LCD screen will be delayed after the load is switched on.
Overload and Short Circuit Recovery
Overload and short circuit automatic recovery time: 5s at the 1
st
time; 10s at the 2
nd
time; 25s at the 3
rd
time; 30s at the 4
th
time; 30s at
the 5
th
time, or automatic recovery the next day.
Load switched on
Load switched off
Short press the key