HPE MSA Controller
Module Replacement
Instructions

©

 Copyright 2013, 2017 Hewlett Packard Enterprise Development LP

*Q1J79-62018*

Part Number: Q1J79-62018
Published: September 2017
Edition: 5

Abstract

This document details procedures for replacing a failed
controller module in an HPE Modular Smart Array
system.

About this document

• The SMU (Storage Management Utility) and the CLI

can be used to manage the enclosure. Tasks in this
document demonstrate using the SMU. Refer to the
SMU reference guide, or the CLI reference Guide for
instructions using those interfaces.

• For the latest product documentation, see the HPE

Support Center website 

http://www.hpe.com/

support/hpesc

.

Before you begin

Observe the following:

CAUTION:

• Removing a module from an operational

enclosure significantly changes air flow within
the enclosure. Openings must be populated for
the enclosure to cool properly. Leave modules
in the enclosure until a replacement is
available.

• Parts can be damaged by electrostatic

discharge; use proper anti-static protection.
Keep parts in electrostatic containers until
needed and ensure you are properly grounded
when touching static-sensitive components.

IMPORTANT:

When replacing both controllers in an operational
enclosure, do as follows:

1.

Replace one controller as detailed in these
instructions.

2.

Wait 30 minutes. This pause ensures that the
controller and its ownership of the vdisks or
disk-groups have enough time to fully stabilize.

3.

To ensure that the system is stable, check the
system status and event logs.

4.

Replace the other controller as detailed in these
instructions.

IMPORTANT:

When two controllers are installed in an enclosure,
they must be the same model and the same
firmware version. Mixing controller types or
firmware versions in the same enclosure is not
supported.

Page 1

Содержание MSA

Страница 1: ...in the enclosure Openings must be populated for the enclosure to cool properly Leave modules in the enclosure until a replacement is available Parts can be damaged by electrostatic discharge use proper anti static protection Keep parts in electrostatic containers until needed and ensure you are properly grounded when touching static sensitive components IMPORTANT When replacing both controllers in...

Страница 2: ...ings NTP settings System information name contact location and description User information Email notification settings SNMP notification settings syslog notification settings Scheduled tasks Hosts IDs and names Specific host IDs names and mappings For more information regarding these settings see the applicable MSA SMU documentation at http www hpe com info storage docs Partner Firmware Update du...

Страница 3: ...e Cache Status LED is off or it is flashing one tenth of a second ON and nine tenths of a second OFF In a single controller environment I O must be stopped and the enclosure must be powered off prior to the replacement In a dual controller environment if the failed controller is first shut down the controller may be hot replaced in an operational enclosure Procedure 1 If you are replacing a contro...

Страница 4: ... need replacing or installing wait 30 minutes before proceeding with those procedures This time frame ensures that one or more controllers and their ownership of vdisks or disk groups are fully stabilized Verifying proper operation Examine the module status as indicated in LED descriptions If the replacement controller does not boot up as expected or if the Fault Service Required LED is amber the ...

Страница 5: ... http www hpe com support msa1040 MSA 1040 product page http www hpe com support msa1040 P2000 G3 MSA manuals page http www hpe com support p2000G3msa P2000 G3 MSA product page http www hpe com support p2000G3msa HPE Passport for MSA arrays http h20564 www2 hpe com hpsc doc public display docLocale en_US docId emr_na c05349541 Documentation feedback Hewlett Packard Enterprise is committed to provi...

Отзывы: