136
RTN cables are covered with insulating sheath, so the labels only need to contain "AC" and the
cabinet number. The labels for AC power cords are affixed to one side of the identification plates on
cable ties.
Table 91 Information on labels affixed to AC power cords
Content Meaning
MN-AC
MN: Rack number (row number and column number in the equipment room) or the
location of the socket where the power is led in.
The location of the socket is marked according to onsite situation. If the sockets can be
identified by row number and column number, they can be numbered following the same
rule for the rack number. Otherwise, specify the detailed locations to avoid confusing
with other sockets.
The label only carries location information about the peer equipment and the power socket, while
information of the local end is not necessary. Make sure labels are affixed in the correct direction.
That is, after the cable ties are bundled onto the cable, the identification plates with the labels should
face up, and the text on the labels in the same cabinet must be in the same direction, as shown
in
:
Figure 91 Example of labels on an AC power cord
•
A01-AC (loaded cabinet side)
—The power cord is connected to the socket of Row A and
Column 01 in the equipment room.
•
B01-AC (power socket side)
—The power cord is connected to the loaded cabinet of Row B,
Column 01 in the equipment room.
Engineering labels for devices
These labels can be affixed to any device.
You can fill in the device name, model, IP address, serial number, installation address, and
installation date on a device label.