Specifications
Environmental specifications
Specification
Value
System inlet temperature (standard operating
support
—
Operating
10°C to 35°C (50°F to 95°F)
Nonoperating
-30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
—
Operating
8% to 90%
28°C (82.4°F), maximum wet bulb temperature
Nonoperating
5% to 95%
38.7°C (101.7°F), maximum wet bulb temperature
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305 m (1.8°F per 1,000 ft) to 3,050
m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The
upper limit and rate of change might be limited by the type and number of options installed. Under standard operating
support, a fan fault or the ambient temperature exceeding 30°C (86°F) might result in reduced system performance
issue.
Limited system operating temperature requirements
The maximum system operating temperature for most components installed in the server is 35°C (95°F).
However, some components in specific configurations are subject to thermal limitations. To ensure safe
and reliable system operation, observe the limited operating temperature for these configurations.
Temperature requirements for transceiver installation in the QSFP port
The following temperature values are valid for systems that have a homogenous node configuration.
Marvell ThunderX2
processor model
OCP network
adapter present
QSFP port cable
type
Maximum inlet ambient
temperature
CN9975-2000 (150 W TDP) No
──
35°C (95°F)
Yes
Copper
35°C (95°F)
Yes
Fiber optic
27°C (80.6°F)
CN9980-2200 (180 W TDP) No
──
23°C (73.4°F)
Table Continued
Specifications
45