Connecting the ERM to the UPS 

 

  

NOTE:

  To install a second ERM, plug the cable from 

the second ERM into the socket at the rear of the first 
ERM. Up to two ERM units can be connected. 

 

Switching on the ERM circuit breaker 

 

 

Charging the ERM batteries 

Connect the UPS to a grounded utility power outlet. When the 
UPS is plugged in, it automatically enters Standby mode and 
begins charging the ERM batteries. With the UPS in Standby 
mode, allow the ERM batteries to charge for at least 24 hours 
before putting the UPS into service. 

  

CAUTION:

  To ensure maximum runtime, be sure to 

configure the UPS for the number of installed ERMs 
using the UPS front panel controls. 

 

 

 

Configuring the UPS 

After the ERMs are installed, place the UPS in Configure 
mode, and use the UPS front panel controls and LED 
indicators to configure the UPS for the number of attached 
ERMs. Other UPS parameters that can also be configured  
are the nominal utility voltage level and Site Wiring  
Fault detection. 

In Configure mode, the LED front panel display changes 
function to enable modification of the UPS parameters. Each 
LED is associated with a different parameter. 

     

Available 
settings 

Parameter  

Associated 
LED 

Explanation (when LED is 
illuminated) 

Nominal 
Voltage 
Setting 

200/208 
Nom 

General 
Alarm 
(red) 

Nominal utility voltage 
level is set to 200/208 
VAC (factory default for 
326529-D71) 

 

220 Nom 

On 
Battery 
(red) 

Nominal utility voltage 
level is set to 220 VAC 

 

230 Nom 

Battery 
Fault (red) 

Nominal utility voltage 
level is set to 230 VAC 
(factory default for 
326529-B31) 

 

240 Nom 

Site 
Wiring 
Fault (red) 

Nominal utility voltage 
level is set to 240 VAC 

Wiring 
Fault 
Setting 

Wiring Fault  Utility 

(green) 

Audible alarm sounds 
when ground is missing or 
line and neutral 
connections are reversed 

ERM 
Setting 

0 ERMs 

0% to 
25% load 
(green) 

UPS is configured for no 
attached ERMs (factory 
default) 

 

1 ERM 

26% to 
50% load 
(green) 

UPS is configured for 1 
attached ERM 

 

2 ERMs 

51% to 
75% load 
(green) 

UPS is configured for 2 
attached ERMs 

 

To change the UPS configuration parameters: 

1.

 

Place the UPS in Configure mode.  
The LEDs associated with the currently configured 
parameters illuminate. A flashing green cursor indicates 
where you are in the configuration process as you scroll 
through the available settings. 

2.

 

To change the nominal voltage, press the On button to 
advance the cursor to the LED associated with the 
appropriate nominal voltage parameter. The selected 
voltage configuration LED flashes. 

Содержание UPS R5500 ERM

Страница 1: ...nance and service of this product must be performed by individuals who are knowledgeable about the procedures precautions and hazards associated with AC power products 75 kg 167 lb This symbol indicates that the ERM exceeds the recommended weight for one individual to handle safely WARNING To reduce the risk of personal injury or damage to the equipment observe local occupational health and safety...

Страница 2: ...ections to the branch circuit such as the use of power strips Electrical requirements All models require a dedicated unshared branch circuit suitably rated for the specific UPS as stated in Input specifications in the user guide Readying the equipment 1 Check the battery recharge date specified on the label that is affixed to the shipping carton IMPORTANT Do not use the battery if the recharge dat...

Страница 3: ... rails for integrated shipping If the unit is to be shipped in an HP 9000 or 10000 series rack 1 Remove the hex nuts flat washers and lock washers from the mounting rail 2 Install the rail reinforcement plates and tighten using the hex nuts with captive washers included in the kit instead of the nuts included with the rail 3 Install the rear mounting brackets using hex nuts Wait until the unit is ...

Страница 4: ... a hazardous condition CAUTION Always plan the rack installation so that the heaviest item is on the bottom of the rack Install the heaviest item first and continue to populate the rack from the bottom to the top 1 Install the mounting rails Installing the mounting rails on page 2 2 With one person on each side of the carton lift the chassis and lower it to the floor in front of the rack 3 Install...

Страница 5: ...t parameter Available settings Parameter Associated LED Explanation when LED is illuminated Nominal Voltage Setting 200 208 Nom General Alarm red Nominal utility voltage level is set to 200 208 VAC factory default for 326529 D71 220 Nom On Battery red Nominal utility voltage level is set to 220 VAC 230 Nom Battery Fault red Nominal utility voltage level is set to 230 VAC factory default for 326529...

Страница 6: ...onfigure mode press the Test Alarm Reset button NOTE Configure mode times out after 2 minutes If the Test Alarm Reset button has not been pressed any new selections are not saved UPS front panel controls The front panel is shown with the bezel removed Item Description Function 1 On button Powers up the UPS 2 Standby button Places the UPS in Standby mode 3 Test Alarm Reset button Silences UPS alarm...

Отзывы: