Verifying the tape drive installation
Procedure
1.
To ensure proper operation, install a drive bay cover on any unused drive bay.
2.
Power on the drive from the OCP or RMI, if necessary.
3.
Confirm that the library recognizes the new tape drive by checking the System Status screen on the
OCP.
If recognized, the new drive will show
Ready
,
RDY
, or
Empty
status.
4.
Use Library & Tape Tools (L&TT) to verify that the host sees the tape drive.
You can download L&TT without charge from:
http://www.hpe.com/support/TapeTools
5.
Use the OCP or RMI to verify that the library sees the tape drive and to update the drive firmware, if
necessary.
Installing an expansion module
Prerequisites
Tools required
• Two small flat head screwdrivers or Torx drivers
• #2 Phillips screwdriver
Procedure
2.
Power off the library and verify that the robotic assembly is in the base module.
For details, see
3. Move a cover to the new module
4.
Install the rack shelves. See
Installing the shelves in the rack
5. Install the module in the rack
6. Align and connect the module
7. Optional: Install tape drives and power supplies
9. Verify the installation and configuration
Planning the installation
Procedure
1.
Decide whether to install this module above or below the current library modules.
Verifying the tape drive installation