Diagnostics
56
Figure 13: Event Log
Were one or more event codes found?
NO
YES
↓
Return to the MAP step that sent you here.
24
Are you at the director reporting the problem?
YES
NO
↓
25
Is the power LED (green) at the director front bezel illuminated?
NO
YES
↓
26
Is the director connected to facility AC power and powered on?
NO
YES
↓
27
Connect the director to facility AC power and set the power switch (circuit
breaker) at the rear of the director to the ON (up) position. Inspect the director for
indications of being powered on, such as: