UPS operations 35
UPS operations
In this section
Initiating a self-test.................................................................................................................................. 35
Silencing an audible alarm...................................................................................................................... 35
Setting the power sensitivity adjustment dial .............................................................................................. 35
Powering down the UPS.......................................................................................................................... 36
Initiating a self-test
A self-test can be performed with equipment connected to the UPS output receptacles. To initiate a self-test,
press and hold the Mute/Test button until the alarm beeps two times.
CAUTION:
Do not unplug the UPS to test the batteries. This action removes safe electrical grounding and
can introduce a damaging surge into the network connections.
The self-test lasts approximately 10 seconds as the UPS switches to battery power to test the load capacity
and battery charge. During the self-test, the Power LED flashes, the Output Load Level LED illuminates, and
the Battery Charge LED illuminates.
Silencing an audible alarm
Press the Mute/Test button.
IMPORTANT:
•
Although the audible alarm silences, the condition that caused the alarm to sound might still exist.
•
If a utility power failure caused the alarm (the Power LED is flashing green), the alarm silences after
power is restored.
Audible alarm conditions
Alarm type
Condition
Audible alarm
Can alarm be
silenced?
Normal
UPS operating from utility power
No audible alarm
N/A
UPS on battery
UPS operating on battery power
On–four short beeps
Yes
Shutdown imminent Batteries nearly out of power
On–continuous
Yes
Battery problem
Batteries must be recharged On–intermittent
beeps Yes
Overload
UPS power capacity exceeded
On–continuous
Yes
Setting the power sensitivity adjustment dial
The power sensitivity adjustment dial is normally set in the counter-clockwise position, enabling the UPS to
provide maximum protection against waveform distortions in the AC input. When distortion occurs, the
Содержание R2200 INTL
Страница 1: ...HP R T2200 UPS User Guide October 2006 Third Edition Part Number 404314 003 ...
Страница 14: ...Installation 14 1 Remove the UPS front bezel 2 Attach the logo badge above the LED Control panel ...
Страница 17: ...Installation 17 ...
Страница 28: ...Installation 28 1 Attach the logo badge above the LED Control panel ...
Страница 30: ...Installation 30 ...
Страница 40: ...Maintenance 40 3 Disconnect the battery leads 4 Remove the battery bracket 5 Remove the UPS battery modules ...
Страница 51: ...Warranty information 51 Notification from power management software ...