System Unit
Chassis Dimensions
(H x W x D) Add fan
extension kit
(with bezel)
7.47 x 17.45 x 35.34in (18.96 x 44.33 x 89.97cm)
NOTE:
Rack chosen is required to have 1200mm depth to provide space for cable
management arm at the rear of the chassis and host PDU in the rear of the rack.)
Weight
(approximate)
Maximum
(all hard drives, power
supply, and processor
installed)
220lb (99.8kg)
Input Requirements
(per power supply)
Rated Line Voltage
100 to 120 VAC
200 to 240 VAC
Rated Input Current
For 1200 W Power Supply:
10 A (at 100 VAC),
4.9 A (at 200 VAC)
For 750 W Power Supply:
8.9 A (at 100 VAC),
4.3 A (at 200 VAC)
Rated Input Frequency 50 to 60 Hz
Rated Input Power
For 1200 W Power Supply:
930 W (at 100 VAC),
1348 W (at 200 VAC)
For 750 W Power Supply:
857 W (at 100 VAC),
824 W (at 200 VAC)
Power Supply Output
(per power supply)
Rated Steady-State
Power
For 1200 W Power Supply:
800 W (at 100 VAC),
900 W (at 120 VAC),
1200 W (at 200 to 240 VAC)
Maximum Peak Power For 1200 W Power Supply:
800 W (at 100 VAC),
900 W (at 120 VAC),
1200 W (at 200 to 240 VAC)
For 750 W Power Supply:
750 W (at 100 to 120 VAC),
750 W (at 200 to 240 VAC)
Power Specifications
To review typical system power ratings use the HP Power Advisor which is available via
the online tool located at URL:
www.hp.com/go/proliant-energy-efficient
or
www.hp.com/go/hppoweradvisor
.
Power Supply Output
(per power supply)
Rated Steady-State Power
System Inlet
Temperature
Operating
50° to 95° F (10° to 35° C) at sea level with an altitude derating
of 1.8°F per every 1000 ft (1.0°C per every 304.8 m) above sea
level to a maximum of 10,000 ft (3048 m), no direct sustained
sunlight. Maximum rate of change is 18°F/hr (10°C/hr). The
upper limit may be limited by the type and number of options
installed.
System performance may be reduced if operating with a fan
QuickSpecs
HP ProLiant SL4540 Generation 8 (Gen8) Server
Technical Specifications
DA - 14406 Canada — Version 19 — June 10, 2014
Page 44