System Unit
Dimensions
(H x W x D)
(with bezel)
6.94 x 19 x 26.5 in (17.6 x 48.3 x 67.3 cm)
Weight
(approximate)
Maximum
(all hard drives, power
supplies, and processors
installed)
95 lb (43 kg)
Minimum
(one hard drive, power
supply, and processor
installed)
79 lb (36 kg)
Input Requirements
(per power supply)
Rated Line Voltage
90 - 132 VAC,
180 - 264 VAC
Rated Input Current
12 A (at 100 VAC),
8 A (at 200 VAC)
Rated Input Frequency
47 to 63 Hz
Rated Input Power
1161 W (at 100 VAC),
1598 W (at 200 VAC)
BTU Rating
Maximum
3985 BTU/hr (at 100 VAC),
5457 BTU/hr (at 200 VAC)
Power Specifications
To review typical system power ratings use the Power Calculator which
is available via the online tool located at URL:
http://h30099.www3.hp.com/configurator/calc/Power%20
Calculator%20Catalog.xls
Click on the system of interest. Example: DL585 G2
Follow the instructions of the next screens
Power Supply Output
(per power supply)
Rated Steady-State
Power
910 W (at 100 VAC),
1300 W (at 200 VAC)
Maximum Peak Power
960 W (at 100 VAC),
1420 W (at 200 VAC)
System Inlet
Temperature
Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change
is 10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed.
System performance may be reduced if
operating with a fan fault or above 30°C
(86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C
(82.4°F) maximum wet bulb temperature, non-
condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature,
non-condensing.
QuickSpecs
HP ProLiant DL585 Generation 2
Technical Specifications
DA - 12575 U.S. QuickSpecs — Version 28 — 11/27/2007
Page 40