Specifications 97
supply circuit and the earthing conductor, and also the point of earthing of the DC system.
The DC system must be earthed elsewhere.
•
The DC supply source is to be located within the same premises as the equipment.
•
Switching or disconnecting devices must not be in the earthed circuit conductor between
the DC source and the point of connection of the earthing electrode conductor.
CAUTION:
To reduce the risk of electric shock or energy hazards:
•
This equipment must be installed by trained service personnel, as defined by the NEC and
IEC 60950-1, Second Edition, the standard for Safety of Information Technology
Equipment.
•
Connect the equipment to a reliably grounded SELV source. An SELV source is a
secondary circuit that is designed so normal and single fault conditions do not cause the
voltages to exceed a safe level (60 V DC).
•
The branch circuit overcurrent protection must be rated 24 A.
1200 W CS Platinum Plus Power Supply (90% efficiency)
Specification
Value
Input requirements
—
Rated input voltage
100V AC to 240V AC
Rated input frequency
50 Hz to 60 Hz
Rated input current
9.1A to 5.5A
Maximum rated input power
897 W at 100V AC input
1321 W at 200V AC input
Btus per hour
3061 at 100V AC input
4506 at 200V AC input
Power supply output
—
Rated steady-state power
800 W at 100V AC input
900 W at 120V AC input
1200 W at 200V to 240V AC input
Maximum peak power
800 W at 100V AC input
900 W at 120V AC input
1200 W at 200V to 240V AC input
Содержание ProLiant DL385p
Страница 12: ...Customer self repair 12 ...
Страница 13: ...Customer self repair 13 ...
Страница 14: ...Customer self repair 14 ...
Страница 50: ...Removal and replacement procedures 50 o 8 or 16 SFF configuration o 8 LFF configuration ...
Страница 90: ...Cabling 90 Cabling SAS hard drive cabling SFF hard drive cabling SFF cabling with optional drive cage ...
Страница 91: ...Cabling 91 LFF hard drive cabling Optical drive cabling ...
Страница 92: ...Cabling 92 FBWC cabling 8 or 16 drive SFF 8 drive LFF ...
Страница 99: ...Acronyms and abbreviations 99 UID unit identification USB universal serial bus ...