Removal and replacement procedures 38
6.
Remove the capacitor pack.
To replace the component, reverse the removal procedure.
Recovering data from the FBWC
If the server blade fails, use the following procedure to recover data temporarily stored in the FBWC.
CAUTION:
Before starting this procedure, read the information about protecting against
electrostatic discharge ("
Preventing electrostatic discharge
" on page
1.
Set up a recovery server blade station using an identical server blade model. Do not install any internal
drives or FBWC in this server blade. (HP recommends this option.)
2.
Power down the failed server blade ("
" on page
).
3.
Transfer the hard drives from the failed server blade to the recovery server blade station.
4.
Remove the SAS controller (on page
NAND flash module for the Smart
" on page
Removing the SAS controller capacitor
" on page
) from the failed server blade, and install the controller, NAND flash module, and
capacitor pack in the recovery server blade.
5.
Power up the recovery server blade.
If data was saved on the NAND flash module, then a 1792 POST message appears, stating that valid
data was flushed from the cache. This data is now stored on the drives in the recovery server blade.
If the SAS controller fails, use the following procedure to recover data temporarily stored in the FBWC.
CAUTION:
Before starting this procedure, read the information about protecting against
electrostatic discharge ("
Preventing electrostatic discharge
" on page
1.
Set up a recovery server blade station using an identical server blade model. Do not install any internal
drives or FBWC in this server blade. (HP recommends this option.)
2.
Power down the failed server blade ("
" on page
).
3.
Transfer the hard drives from the failed server blade to the recovery server blade station.