Management module 37
Connecting an alarm device to the management
module alarm relay
An alarm device can be connected to the management module alarm relay through the RJ-12 connector. You
can enable or disable the alarm relay for specific alarms and warnings through the web interface. 24 V DC
up to 100 mA is available directly from the management module or the alarm relay can switch up to 30 V at
1 A. For more information, see the
HP Modular Cooling System 200/100 Web Interface User Guide.
NOTE:
The connection to the alarm relays is hard wired. For more information, see connection
description on the management module.
Alarm relay item
Specification
Type of alarm relay
Potential-free change-over contact
Maximum current
consumption
100 mA with internal
or
1 A with external power connection
Maximum voltage
DC, 24 V internal
or
DC, 30 V with external power connection