NS7 System With Two Rack-Mounted UPS in Parallel
shows an example of a non-supported configuration in a NS7 system with the left
PDUs connected to a rack-mounted UPS and the right PDUs connected to a different
rack-mounted UPS. In this configuration, OSM manages and monitors the rack-mounted UPSs.
Figure 26 NS7 System With Two Rack-Mounted UPS in Parallel
OSM has the capability to monitor both UPSs, but it does not have the logic to initiate the controlled
shutdown of the I/O operations and processors when utility power fails in this configuration.
If the utility power is not restored before both rack-mounted UPSs shut down, any data in the
NS7 system disk drive write cache that has not been transferred to the disk drive media is lost.
If you want to extend the UPS battery runtime, Hewlett Packard Enterprise recommends adding
Extended Runtime Modules (ERMs) to the UPS.