Dimensions and Weights for NS7 AC Systems
This subsection provides the dimensions and weights for racks and enclosures.
Plan View of the Racks
Service Clearances for NS7 Racks
Aisles: 6 feet (182.9 centimeters)
Front: 3 feet (91.4 centimeters)
Rear: 3 feet (91.4 centimeters)
Unit Sizes for NS7 Systems
Height (U)
Enclosure Type
42 or 36
Rack
10
c7000 enclosure
2
CLIMs
2
SAS disk enclosures
1
CLIM patch panel (RJ45 and Fiber)
1
FDR IB ADI switch
1
FDR IB managed switch, expansion
1
IB FDR managed switch, IB cluster
1
Maintenance switch (Ethernet)
3
R5000 UPS (single-phase power)
3
ERM for single-phase UPS
6
R12000/3 UPS (three-phase power)
3
ERM for three-phase UPS
50
NS7 System Installation Specifications