Subtleties of power capping 

Avoiding power capping conflicts within groups 

Insight Control is a powerful tool for setting and managing power caps across defined groups of servers, including 

SIM collections. It is important to remember, however, that except for Enclosure Dynamic Power Capping, power 
caps are ultimately set at the individual server level. Insight Control apportions a group power cap as individual 
power caps to all of the servers in the group.  
Power capping is also completely non-hierarchical. A power cap set using Insight Control has no precedence over a 
power cap set using the iLO interface. Each server conforms to the last power cap that it received, regardless of the 
method used to set it. 
For example, consider this situation: A server is a member of two distinct SIM collections. An administrator applies a 
group power cap to each of these collections. The individual power caps of servers in both collections will be the 

last cap applied to either collection. Later an administrator uses the iLO interface to set a power cap on an 
individual server within one of the collections. For that server, the new cap will replace the previous power cap that 
had been set through Insight Control.  
A similar situation can occur when administrators use Insight Control to set enclosure dynamic power caps for 
groups of enclosures. Setting a new cap on a single enclosure through its OA can overwrite a group power cap 

previously apportioned to the individual enclosures.  
This potential overlap in setting power caps is important to consider when planning and implementing an overall 
power capping/capacity management strategy. Choosing a single consistent method for setting power caps is the 

best way to avoid conflicts. For example, a system administrator could define a set of non-overlapping SIM 
collections used specifically for power and cooling management. 

Powering up groups of servers when using Dynamic Power Capping 

HP Dynamic Power Capping is a powerful tool for controlling the steady-state power consumption of servers in real 
time. However, it does not control the power consumption of servers at start-up when their maximum power 

consumption is measured. If a group of servers on the same PDU power-up simultaneously, there will be a window 
during start-up before Dynamic Power Capping is active. During that window, the servers will draw close to their 
maximum power at roughly the same time. If this peak is too large, it may cause problems. Therefore, it is important 

to manually power on these server groups in a staggered manner. Administrators using the iLO interface or the 
enclosure OA for BladeSystem servers can stagger auto power-ups by enabling the servers’ Power On Delay and 

setting it to “Random up to 120 seconds.”  

Setting low or unattainable power caps on servers 

In theory, administrators can set a power cap to any value above the minimum power consumption for a given 
server or a group of servers. However, setting power cap values close to the minimum power consumption is not 
good practice. Maintaining a power cap at or near this level prevents the server from accomplishing meaningful 

work. Also, a server’s minimum power consumption level may rise over time for a number of causes, including 
increased fan activity as data center temperatures rise or hot-adding disk drives to the server. A power cap 
becomes unachievable if the minimum power consumption of the server rises above it. In this situation, the capping 

subsystem will cap the power consumption as low as it can and report that the power cap is unachievable.  
Best practice is to re-evaluate the cap value after adding any hardware to the server, and to use power caps that 

are at least halfway between the minimum and maximum power consumption for a server or server group. Both the 
iLO and Insight Control interfaces provide a warning when a power cap value is lower than this. 
Enclosure Dynamic Power Capping has resolved much of this issue. It disallows enclosure power caps that are too 

close to the aggregate minimum power for the enclosure and its server blades. However, setting a very low cap 
value for the enclosure can prevent blades in the enclosure from accomplishing meaningful work. 

Содержание Integrity NonStop NB54000c

Страница 1: ...0 Setting power caps for servers 10 Setting a power cap for a single server 11 Setting a power cap for a group of servers 13 Setting a BladeSystem enclosure power cap 13 Setting a power cap for a group of enclosures 14 Using power capping in data center provisioning 15 Choosing effective power caps 15 Power capping to peak power consumption 17 Power capping to average power consumption 19 Using En...

Страница 2: ...Providing a guardband for a power capping group 23 Summary 24 For more information 25 Call to action 25 ...

Страница 3: ...a given computational workload Power capping simply limits the amount of power that a server can use at any point in time This lets you allocate data center power and cooling resources more efficiently In general if a given power cap restricts the amount of power that a server would normally use to perform a task that task will take longer Over time the server will consume about the same total ene...

Страница 4: ...throttling Clock throttling is another method for lowering processor power consumption Depending on the processor model the system BIOS can either reprogram the processor to run at a lower frequency or modulate the processor between running periods and stopped periods Both methods have the same net effect of lowering the processor s overall power consumption below the levels available using P stat...

Страница 5: ...s and even the mix of instructions executed As long as the power consumption remains below the power cap the power capping control mechanism takes no action and there is no affect on server performance Minimum and maximum power consumption for a server The power management system in each server determines both the minimum and maximum power consumption for the server It determines these two values ...

Страница 6: ...Capping as basic Power Capping throughout the remainder of this paper Table 3 Characteristics of Dynamic Power Capping and basic Power Capping Dynamic Power Capping Basic Power Capping Power capping executed from Power management microcontroller iLO and system ROM BIOS Control of processor power Direct hardware connection to processor to control P state clock throttling at the processor hardware l...

Страница 7: ...ht Control One of the most powerful uses of power capping is monitoring and controlling the power use of an entire group of servers This capability is available through Insight Control Administrators can apply a group power cap to any group of servers that they can select within Insight Control including Insight collections Insight Control displays the aggregated minimum and maximum power consumpt...

Страница 8: ...etting a power cap for the enclosure indirectly creates power caps for the server blades within it The Onboard Administrator OA then actively manages these power caps and reallocates power as workloads change over time Elements of an enclosure power cap With Enclosure Dynamic Power Capping an administrator sets a power cap for an entire BladeSystem enclosure not simply for the server blades in the...

Страница 9: ... The OA maintains the overall enclosure cap by monitoring and managing the power consumption of the server blades To accomplish this the OA collects the overall enclosure power use and the total power used by the managed server blades From this data the OA constructs a blade power budget representing the amount of power that the blades can consume while keeping the overall enclosure power consumpt...

Страница 10: ...er their caps within the 3 seconds required for normal circuit breaker protection However the redundant side of the enclosure power can absorb the transient overage until overall power consumption is again under the enclosure cap If N N power redundancy fails then a hardware based failsafe mechanism overrides the Enclosure Dynamic Power Capping and immediately lowers all server blade processors to...

Страница 11: ...through Insight Control In the iLO 2 browser based interface Figure 5 Power Capping Settings is located beneath the Power Management tab in the Settings subsection The iLO 2 Power Management Settings screen indicates whether the server supports Dynamic Power Capping Figure 5 Setting a power cap for an HP BladeSystem server using iLO 2 ...

Страница 12: ... Insight Control Power Capping is located beneath the HP Power Management Actions section of the interface as shown in Figure 6 Figure 6 Setting a power cap for an HP BladeSystem server using Insight Control ...

Страница 13: ...and the power supply rating of the entire group Figure 7 Setting a group power cap in Insight Control Setting a BladeSystem enclosure power cap You can use either the OA or Insight Control to set the power cap for a BladeSystem enclosure to any value between the power cap lower bound and the maximum available power for the enclosure Figure 8 shows the Power Management screen from HP Onboard Admini...

Страница 14: ...The lower bound of the power cap is 15499 watts It is higher than the maximum power measurement because it represents the lowest reasonable power cap for the group that is sustainable under all operating conditions Applying a power cap value of 25 000 watts to the group causes Insight Control and the OAs to create and apply a separate Enclosure Dynamic Power Cap to each of the five enclosures usin...

Страница 15: ...apping takes this one step further Its ability to control server power consumption in real time allows administrators to use power capping for planning and managing both their electrical provisioning and their cooling infrastructure Choosing effective power caps Setting an effective power cap involves determining the lowest value for the power cap that will still meet the power requirements for a ...

Страница 16: ...d use under environmental and load conditions It is one of the numbers that an administrator could use when calculating the maximum power and cooling requirements to support this system in the data center For a rack containing a group of eight of these servers the total requirements would be 3384 watts Figure 10 HP Power Calculator results for a configured ProLiant DL380 G5 server ...

Страница 17: ... the history of peak and average power consumption for the group provides a good starting point for deciding how to set effective power caps that meet different power management objectives in the data center Power capping to peak power consumption As the power consumption graph in Figure 11 shows peak power consumption for the eight server group running this workload is consistently about 3116 wat...

Страница 18: ...r Capping applied the same circuit can support over 10 more servers if all 10 have the same power cap as the first eight servers Table 5 Power provisioning for eight DL380 G5 servers when capping to peak power consumption using Dynamic Power Capping Description Power Traditional input power provisioning for 8 DL380 G5 servers 1217 input VA at 208 volts de rated by 20 percent 7760 watts 970 x 8 Max...

Страница 19: ...o average 1900 watts Guardband 190 watts Savings in power capacity 1294 watts Additional servers that can be provisioned within the same cooling infrastructure 5 Dynamic Power Capping will more significantly affect any workload transients exceeding the cap Therefore HP recommends capping a server group supporting Dynamic Power Capping at the average power consumption only in applications where pea...

Страница 20: ...of servers using Insight Control and power capping This will quickly lower server power consumption and heat generation in the affected area until you can restore cooling Under these circumstances it may be appropriate to set power caps significantly lower even though they may affect performance Using HP SIM you can define and store groups of servers as collections This allows you to apply power c...

Страница 21: ...u access this scheduling capability using the Configure Power Management Power Usage Controls menu Task scheduling consists of several steps including defining the new power cap Figure 13 and creating the schedule for applying the power cap Figure 14 Figure 13 Setting a power cap as part of a scheduled task Figure 14 Defining the scheduled Insight Control task in Systems Insight Manager Constructi...

Страница 22: ...ng the steady state power consumption of servers in real time However it does not control the power consumption of servers at start up when their maximum power consumption is measured If a group of servers on the same PDU power up simultaneously there will be a window during start up before Dynamic Power Capping is active During that window the servers will draw close to their maximum power at rou...

Страница 23: ...or manages server power use as long as a server s power consumption remains below the power cap setting Power capping will override Power Regulator only if power consumption exceeds the established power cap Power capping and CPU utilization Both power capping and Power Regulator involve manipulating the system processor at a very basic level As a result power capping can affect the processor util...

Страница 24: ...to make significant hardware or environmental changes for one or more servers should increase guardband to the group total to allow for the changes However best practice is to re evaluate the server caps after adding hardware and to select caps that are at least halfway between the minimum and maximum power consumption for a server or server group When you follow best practices additional guardban...

Страница 25: ...ogy brief http h20000 www2 hp com bc docs support SupportManual c00300430 c00300 430 pdf Power Regulator http h18013 www1 hp com products servers management ilo power regulator html Call to action Send comments about this paper to TechCom HP com Copyright 2008 2009 2010 Hewlett Packard Development Company L P The information contained herein is subject to change without notice The only warranties ...

Отзывы: