88
Figure 55
Binding cables where they must be bent
•
Route, bind, and attach excess cables for easy and safe maintenance and correct operation.
•
Do not tie power cables to slide rails.
•
When you connect a cable to an articulated part, such as connecting a grounding cable to a
cabinet door, leave enough slack in cables and make sure they are not stressed from any movement
of the part.
•
Cables must be protected at points where they might rub or come in contact with sharp edges or
heated areas. Use high temperature cables near heat sources.
•
Securely fasten cables and take adequate measures to prevent loose connections.
Figure 56
Securely fastening cables
(1) Flat washer
(2) Spring washer
(3) Nut
•
Fasten heavy or rigid power cables at the connectors to relief stress.
•
Do not use tapping screws to fasten the connecting terminals.
•
Bind together cables that are the same type and routed in the same direction.
lists the cable bundling specifications.
Table 51
Tie-binding parameters
Cable bundle diameter (mm)
Space between bundles (mm)
10
80 to 150
10 to 30
150 to 200
(1) (1)(2)
(3)
(1) (1)(2)
(3)