Table 8 Compute enclosure 3-phase HP 2400 W power supply specifications (North America/Japan)
(continued)
Value
Specification
3.0m (10ft)
24.0 A at 200 VAC
Max input current per line cord
23.1 A at 208 VAC
Input requirements
200 VAC to 240 VAC line-to-line 3–phase
Rated input voltage
50–60 Hz
Rated input frequency
100 A for 10 ms
Maximum inrush current
3.5 mA
Ground leakage current
0.98
Power factor correction
Table 9 Compute enclosure 3-phase HP 2400 W power supply specifications (International)
Value
Specification
IEC-309 220–240V, 5–pin, 16 A
Power cords (4)
3.0m (10ft)
12.1 A at 220 VAC
Max input current per line cord
11.1 A at 240 VAC
Input requirements
200 VAC to 240 VAC line-to-neutral 3–phase
Rated input voltage
50-60 Hz
Rated input frequency
100 A for 10 ms
Maximum inrush current
3.5 mA
Ground leakage current
0.98
Power factor correction
Table 10 Compute enclosure power requirements
VA
Watts
Power required (50–60 Hz)
9000
8820
User expected maximum power
1
1
Typical maximum Power or User expected maximum power (Input power at the ac input expressed in Watts and Volt-Amps.)
This figure was developed with the absolute maximum configuration running applications designed to draw the maximum
power possible. It is highly unlikely that any real-world application will result in this amount of power use for any significant
time period.
24