CSI Section 16160

Siemens Electrical Products and Systems

Specification Guide

AC

Controls

15

Key Features

Fully NEMA Rated Sizes 00–8

Double Break Contacts 

Silver Tin Oxide Contacts, Cadmium-
Free (Sizes 00–5)

Higher Locked Rotor Current Ratings,
Up to 840% (Sizes 00–5)

Arc Chutes with Arc Splitters; Fast Arc
Quenching                    .

Lowest Contact Bounce (2
Milliseconds or less on Most Sizes) 

Touch Safe Power Terminals 
(Sizes 00–3)

Touch Safe Control Terminals 
(Sizes 00–5)  

Snap-on 2 NO and 2 NC Auxiliary
Contacts Standard (Sizes 00–5)

Visual ON / OFF indicator 

Color-Coded Coils

Fast Termination System — Wire
Funnels, Wire Stops, Screwdriver
Guide Holes, and Captive Hardware

Long Mechanical Life 
— 15 Million (Size 00)
— 10 Million (Size 0–5)
— 5 Million (Size 6–8)

UL Listed and CSA Certified

AC Controls

Contactors — Non-Reversing

General

Amps

Ampere Rating (Open)

Measured Parameter

8

1350

7

900

6

600

5

300

4

150

3

100

2

50

1

30

0

20

00

10

Amps

Ampere Rating (Enclosed)

1215

810

540

270

135

90

45

27

18

9

Volts

Maximum Voltage Rating

600

600

600

600

600

600

600

600

600

600

HP

Squirrel Cage
Motor Maximum
Horsepower

150

75

40

25

10

7.5

3

1.5

kW

kW

kVA

kVA

230 V, 60 Hz

200 V, 60 Hz

450

300

200

100

50

30

15

7.5

3

1.5

380 V, 50 Hz

300

150

75

50

25

10

5

1.5

460–575 V, 60 Hz

Resistive
Heating
(1-Phase
2-Pole)

240 VAC

120 VAC

480 VAC

600 VAC

Resistive
Heating
(3-Phase
3-Pole)

Capacitor
Switching
(3-Phase)

240 VAC

120 VAC

480 VAC

600 VAC

Transformer
Switching
(1-Phase
2-Pole)

240 VAC

120 VAC

480 VAC

600 VAC

Transformer
Switching
(3-Phase
3-Pole)

AC Coil
Ratings

240 VAC

208 VAC

480 VAC

600 VAC

Overall

Inrush

Sealed

240 VAC

480 VAC

600 VAC

900

600

400

200

100

50

25

10

5

2

90

60

30

15

10

5

3

180

120

60

30

20

10

6

360

240

120

60

40

20

12

450

300

150

75

50

25

15

155

105

52

26

17

8.5

5

315

210

105

68

34

17

10

625

415

210

105

68

34

20

775

515

260

130

86

43

25

360

240

160

80

40

27

12

KVAR

720

480

320

160

80

53

25

900

600

400

200

100

67

31

61

41

27

14

6.8

4.1

2.1

1.2

0.6

122

81

54

27

14

8.1

4.1

2.4

1.2

244

162

108

54

27

16

8.3

4.9

2.4

304

203

135

68

34

20

10

6.2

3

182

122

81

41

30

12

6.3

3.6

1.8

210

140

94

47

23

14

7.2

4.3

2.1

420

280

188

94

47

28

14

8.5

4.2

525

351

1350

117

59

35

18

11

5.2

Hz

60

60

60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

VA

4200

4000

2900

2450/2960

910/1090

330/410

183/233

101/32

101/32

68/87

VA

100

140

105

115/146

58/70

32/39

17/21

12.1/16.1

12.1/16.1

10/12

MS

to 10% overvoltage,
(warm or cold coil) Total
Opening Time Includes
Arcing Time Closing Delay

Operating
Times
(valid for 20%
Undervoltage)

40–80

30–50

30–50

17–65

20–50

15–40

20–50

13–67

13–67

10–35

G/MS

Operating

140–240

10–20

10–20

18–30

20–40

15–35

15–35

15–20

15–20

15–30

AWG

Resistance To Shock (Rectangular pulse)

8.8/5 4.9/10

10.4/5 5.8/10

8.6/5  4.8/10

9.2/5  4.8/10

5.7/5 9/5

5.7/5 9/5

5.5/5 3.2/10

AWG

Conductor size/phase

(4) 2/0–500MC

(3) 2–600MCM

(2) 4–500

1-500MCM

2-300MCM

10–1/0

10–1/0

10–1/0

(2) 14–3

(2) 14–10

MILL

Auxiliary Contact Wire Size

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

(2) 18–12

Mechanical Life (make/break operations)

5

5

5

10

10

10

10

10

10

15

Total Auxiliary Contacts Available

8

8

8

8

8

8

8

4

4

4

Auxiliary Contact Rating A600/P600

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NEMA Size

Table 15.27     Contactor Technical Data

For ratings contact Siemens.

Type 3TF Non-Reversing AC Contactors

NEMA Size 1

NEMA Size 3

NEMA Size 5

Содержание Class MMS and MRS

Страница 1: ... in each speed Class MRS reversing manual switches provide a compact means of starting stopping and reversing AC motors where overload protection is not required or is provided separately They are suitable for use with three phase squirrel cage motors and for single phase motors which can be reversed by reconnecting motor leads Two switches are used one to connect the motor for forward rota tion a...

Страница 2: ... in each speed Class MRS reversing manual switches provide a compact means of starting stopping and reversing AC motors where overload protection is not required or is provided separately They are suitable for use with three phase squirrel cage motors and for single phase motors which can be reversed by reconnecting motor leads Two switches are used one to connect the motor for forward rota tion a...

Страница 3: ... Two Winding 3 Lead Std With Pilot Light 115 and 230 VAC 3 3 Phase and 1 Phase Capacitor Split Phase 4 Lead Repul Induct Std With Pilot Light 110 120 208 220 440 600 VAC 2 Single Phase Two Winding 3 Lead Std With 2 Pilot Lights 115 and 230 VAC 3 Three Phase Separate Winding Wye Connected Std With 2 Pilot Lights 208 220 and 440 600 VAC Standard With Pilot Light 115 and 230 VAC 1 2 1 2 2 2 Toggle To...

Страница 4: ...or switch is on left extends 1 62 in 41 mm from mounting surface Device Type of Operator Toggle Key Toggle SMF SMF SMF SMF SMF SMF MRS SMF MMS One Starter Two Starters One Str and One Sel Sw 햲 Reversing Switch 햳 Two Speed Starter Two Speed Switch Table 15 6 Two Unit Devices NEMA Type 1 General Purpose Enclosure FG02 02P FG04P FG222 222P FG44P FG71 71P 72 72P FG74P KG11 11A 11B 22 22A 22B 22C FG11 ...

Страница 5: ...ounting in a NEMA 1 enclosure for flush mounting on a standard depth switch box or in custom panels A pilot light for 120 208 240 or 480 volts may be added at any time before or after installation Wiring Diagrams Dimension Drawings 1 Phase 3 Phase NEMA 1 Open with Flush Plate Type 1 Phase 3 Phase 2 230 575 Volts 115 Volts 120V DC Continuous Amp Rating 3 24 1 2 15 Table 15 9 Class 12 Manual Startin...

Страница 6: ...le Phase 쐍 Class 10 Adjustable Ambient Compensated Overload Protection 쐍 Phase Loss Sensitivity 쐍 Undervoltage Protection UV trip module may be added in field 쐍 Shunt Trip Module is also field adda ble 쐍 Available in Open Styles NEMA 1 and 3R watertight dusttight under table and flush mount enclosures 쐍 1 NO and 1 NC Auxiliary Contacts Standard 쐍 Group Installation UL 508 The 3VU13 is suitable for...

Страница 7: ...lers have front accessible pressure type wire connec tors Ample wiring space is provided for easy wiring A complete line of general purpose and industrial duty enclosures is available as well as open type mounting for custom built enclosures These manual con trollers are available with low voltage pro tection which will automatically open the power poles when the voltage drops or the power is inte...

Страница 8: ...0 279 40 9 700 233 36 Open NEMA 1 NEMA 4 NEMA 4X NEMA 7 9 NEMA 12 Table 15 12 Motor Starters A 2 500 63 50 5 688 114 46 6 250 158 75 7 938 201 62 7 125 184 15 5 875 149 23 B 3 625 92 08 3 188 80 96 5 125 130 18 7 313 185 74 5 875 149 23 5 063 128 59 C 5 500 139 70 5 875 149 23 10 375 263 53 11 125 282 58 9 188 233 36 8 625 219 08 D E 2 250 57 15 2 500 63 50 4 125 104 78 6 875 174 63 6 063 153 99 3...

Страница 9: ...ntactors may be controlled by timers and other pilot devices These contactors are also available with a DC coil and rectifier for reduction of AC hum in noise sensitive areas such as hos pitals schools and similar locations For information and availability of mechanically held lighting contactors contact your local sales office General AC Controls Magnetic Contactors 2 63 0 59 0 34 0 305 0 25 1 49...

Страница 10: ...Dimensions In Inches mm Table 15 16 Type CLB CLF CLN 3 Pole Electrically Held Combination Lighting and Heating Contactors Combination Fusible Non Fusible or Circuit Breaker Ampere Rating 30 6 65 169 14 06 357 6 9 12 6 81 173 60 6 65 169 14 06 357 3 6 81 173 60 9 88 251 20 0 508 6 12 16 0 406 6 48 165 15 0 381 10 75 273 30 5 33 135 10 05 255 3 5 56 141 20 6 65 169 14 06 357 2 12 6 81 173 6 48 165 1...

Страница 11: ...WE90B 21WE72B 21WE62A 21WE44A 21WE90A 21WE72A 4 0 2 4 21WE54B 21WE100B 21WE82B 21WE64B 21WE54A 21WE100A 21WE82A 21WE64A 2 3 4 4 4 6 6 8 8 8 9 9 9 10 10 10 12 12 12 2 3 4 3 2 6 4 8 6 4 9 7 5 10 8 6 12 10 8 0 2 4 21WE120B 21WE102B 21WE84B 21WE120A 21WE102A 21WE84A Type 50 Hz Part No 1 NO 1 NC 2 NO 1 NO 1 NC Table 15 20 Adder Decks 21WS10 21WS01 21WS20 21WS11 2 NC 2 NO 2 NC 4 NO 21WS02 21WT20 21WT02 ...

Страница 12: ...8 10 6 75 171 1 88 48 4 38 111 0 23 6 4 94 125 4 61 117 1 50 38 3 95 100 4 19 106 1 2 3 31 84 5 06 129 4 62 117 7 25 184 3 31 84 4 5 2 3 3 2 4 5 2 9 3 4 13 0 6 3 3 2 A B C D E F G No of Poles Dimensions In Inches mm Figure No Shipping Weight in lbs kg Table 15 22 Type CLM Magnetically Latched 30A to 200A Lighting and Heating Contactors Open Type CLM Contactors 30 to 200 Ampere CLM Contactors 300 a...

Страница 13: ...ng when used open or enclosed Optional solid state control modules are available to allow control of the CLM lighting con tactors directly from energy management systems microprocessors photoelectric cells timers and similar control devices They permit programmable time schedul ing of loads automatic control of lighting near windows to allow the use of natural ambient lighting levels and manual ov...

Страница 14: ...th visible blade contacts for ease of inspection removable line shields and front removable fuse clips and lugs disconnect switches are UL recognized and CSA certified They are available with Class H J and R fuse kits for a wide range of fused non fused and over fusing options AC Controls Combination Starters NEMA Sizes 0 4 General Dimensions Dimensions in Inches mm Table 15 26 Magnetic Motor Star...

Страница 15: ...all Inrush Sealed 240 VAC 480 VAC 600 VAC 900 600 400 200 100 50 25 10 5 2 햲 90 60 30 15 10 5 3 햲 180 120 60 30 20 10 6 햲 360 240 120 60 40 20 12 햲 450 300 150 75 50 25 15 햲 155 105 52 26 17 8 5 5 햲 315 210 105 68 34 17 10 햲 625 415 210 105 68 34 20 햲 775 515 260 130 86 43 25 360 240 160 80 40 27 12 KVAR 720 480 320 160 80 53 25 900 600 400 200 100 67 31 61 41 27 14 6 8 4 1 2 1 1 2 0 6 122 81 54 2...

Страница 16: ...inrush does not produce an objectional voltage drop All starters are supplied with a NO hold ing contact that in conjunction with an appropriate pilot device will provide low voltage protection or release Features Size 0 6 Magnetic Starters include the following standard features Molded Coil Magnetic coils are care fully wound and then sealed in epoxy Encapsulation helps seal out moisture promotes...

Страница 17: ...ion The 45 degree wedge action contacts reduce tracking and provide faster arc quench ing The resulting self cleaning and reduced contact bounce mean cooler operation and longer life for the large silver cadmium oxide contacts Terminal Design Control terminals are self rising pressure type Auxiliary Contacts Front mounted as well as side mounted auxiliary contacts are available A maximum of four c...

Страница 18: ... 121 4 31 109 4 75 121 4 88 124 4 50 114 6 13 156 5 50 140 17 38 441 22 50 572 4 88 124 4 25 110 6 13 156 5 50 140 7 81 198 5 50 140 17 38 441 3 19 81 3 75 95 3 75 95 4 00 102 4 00 102 5 06 129 5 06 129 5 75 146 7 88 200 7 88 200 10 00 254 Size 00 Sizes 0 13 4 Size 00 Size 0 4 Size 41 2 5 Size 6 Fig 1a Fig 1b Fig 2 2 Pole Single Phase Magnetic Contactors 3 Pole 3 Phase Magnetic Contactors Optional...

Страница 19: ...1 2 13 73 4 51 2 2 21 2 16 81 8 61 8 3 26 131 8 713 16 31 2 4 26 131 8 713 16 41 2 5 3913 16 179 16 105 8 6 4513 16 219 16 121 4 NEMA 4 Watertight Enclosures NEMA 4X Watertight Corrosion Resistant Enclosures 0 13 4 13 73 4 55 16 0 21 2 16 81 8 61 16 3 26 131 8 79 16 31 2 4 26 131 8 79 16 41 2 5 3913 16 179 16 109 16 6 4513 16 219 16 119 16 0 2 117 8 75 16 67 8 2 Bimetal 21 2 1411 16 117 8 67 8 3 3...

Страница 20: ...303 CSI Section 16160 Siemens Electrical Products and Systems Specification Guide AC Controls 15 Dimensions Magnetic Contactors Enclosures Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Fig 3b Fig 3a ...

Страница 21: ... Free Feature 쐍 Clear Plastic Sealable Cover to Prevent Unauthorized Tampering 쐍 UL Listed and CSA Certified Starter Types SXL Full Voltage across the line Non Reversing SRL Full Voltage across the line Reversing SCN Full Voltage across the line Non Reversing combination Non Fusible SCF Full Voltage across the line Non Reversing combination Fusible SCB Full Voltage across the line Non Reversing co...

Страница 22: ...tor rated 100 HP at 1200 rpm delivers 50 HP at 600 rpm This type is applicable to conveyors mills dough mixers reciprocating pumps and other similar loads 쐍 Variable Torque HP varies as square of speed while torque varies directly with speed A variable torque motor rated 100 HP at 1200 rpm delivers 25 HP at 600 rpm This type is applicable to drives having fan or centrifugal pump characteristics 쐍 ...

Страница 23: ...06 CSI Section 16160 Siemens Electrical Products and Systems Specification Guide AC Controls 15 General AC Controls Reduced Voltage Starters Electromechanical Typical Speed Torque Curves Auto Transformer Starter Wye Delta Starter Part Winding Starter Table 15 35 of Reduced Voltage Motor Starting Comparison of Various Electromechanical Methods 50 Tap 25 First in order of smoothness 30 seconds Based...

Страница 24: ...controller uses sili con controlled rectifiers SCR s to control the voltage to the motor windings Each SCR acts as a switch that can be turned on with any electronic trigger signal at any point on the voltage waveform and turns off when the current waveform crosses zero Two SCR s are used in a back to back arrangement in each phase to allow alternating current to pass to the motor When SCR trigger...

Страница 25: ...26 660 16 406 13 330 42 55 36 914 20 508 11 279 36 914 20 508 11 279 68 105 46 1168 20 508 10 254 46 1168 20 508 10 254 130 53 1346 25 635 10 254 53 1346 25 635 10 254 192 248 90 2286 20 508 15 381 90 2286 20 508 15 381 361 90 2286 30 762 15 381 90 2286 30 762 15 381 480 90 2286 40 1016 15 381 90 2286 40 1016 15 381 720 90 2286 50 1270 15 381 90 2286 50 1270 15 381 36 914 20 508 11 279 36 914 20 5...

Страница 26: ...rings Black plastic or anodized aluminum rings are optional at no additional cost The plastic rings are recommended for use where the atmosphere may be corrosive LED Indicating Lights Optional Since LED s consume less power their life is 10 to 20 times that of conventional incandescent lamps They also provide greater resistance to shock and vibration Where lamp integrity and low mainte nance is cr...

Страница 27: ...nassembled P30 series stations are available in NEMA 1 3R 4 4X and 13 enclosures Application Class 52 oil tight pilot controls and acces sories are designed to provide long trou ble free service in the most demanding industrial applications These controls are oil and dust tight and meet NEMA 1 3 4 12 and 13 specifications Push Button Operators The operator base consists of a durable one piece cast...

Страница 28: ...nal Starter shall include one normally open auxiliary contact as standard with capabil ity of mounting at least 3 additional Starters shall be equipped with three pole overload relays Overload relay shall be melting alloy type NEMA Class 20 with a test feature An isolated field mountable alarm contact should be avail able Optional Class 10 overload relay should also be available for factory or fie...

Страница 29: ...tarters shall be equipped with a three pole overload relay wired in the phase windings Overload relay shall be a block type NEMA Class 10 with push to test feature phase unbalance and phase loss protec tion be field adjustable and have an iso lated alarm circuit contact For NEMA size 6 8 starters the overload relay shall be a 3UB solid state microprocessor controlled device and have a field adjust...

Отзывы: