background image

This connection is used to access the UPS Network Module remotely 

through the web interface. The UPS Network Module also uses the 

network connection to communicate to the configured HP Power 
Protector — Clients and to facilitate SNMP-based monitoring. 

 

Connecting the configuration 

cable 

1.

 

Connect the DB-9 connector on the DB-9 to RJ-45 cable to a 

serial connector on the host computer. 

2.

 

Connect the RJ-45 connector on the DB-9 to RJ-45 cable to the 
Settings/AUX connector on the UPS Network Module. 

 

This connection is used to access and configure the UPS Network 
Module network settings locally through a terminal emulation 

program. 

 

Launching a terminal emulation 

program 

  

 

NOTE:

  HyperTerminal is the serial communication 

program provided with Microsoft® Windows® and is 

used in this section as an example for setting up a 

terminal emulation session. If you are using another 
utility, the steps might be different. 

  

1.

 

Be sure that the UPS is powered on. 

2.

 

On the host computer, click 

Start, 

and select 

Programs>Accessories>Communications>HyperTerminal.

 

The Connection Description window appears. 

3.

 

Enter a description, select an icon for the connection, and then 
click 

OK.

 The Connect To window appears. 

4.

 

Select the serial connector on the host computer to which the 
DB-9 to RJ-45 adapter is attached, and then click 

OK.

 The 

COM Properties window appears. 

5.

 

Select the following parameter values, and then click 

OK.

 

o

 

Bits per second—9600 

o

 

Data bits—8 

o

 

Parity—None 

o

 

Stop bits—1 

o

 

Flow control—None 

 

Configuring the UPS Network 

Module network settings 

On the terminal emulation session screen running on the host 
computer: 

1.

 

Press any key. The initialization process completes, and you 
are prompted enter the password. 

2.

 

At the prompt, enter 

admin

. The HP UPS Network Module 

Configuration Menu appears. 
Use the HP UPS Network Module Configuration Menu to 
configure the minimum settings required to access the UPS 

Network Module remotely. 

  

 

IMPORTANT:

  The IP address assigned to the UPS 

Network Module must be fixed. If the IP address 

changes: 

 

The HP Power Protector — Client loses 

communication with the UPS Network Module. 

 

You can lose track of the UPS Network Module URL. 

  

3.

 

If your network is configured with a DHCP server, the network 
settings are automatically assigned. To view the settings: 

a.

 

On the Main menu, enter 

2

 to display the Network 

Configuration submenu. 

b.

 

Enter 

1

 to read the network settings. 

c.

 

Record the IP address. 

d.

 

Enter 

0

 to return to the Main menu. 

e.

 

Enter 

0

 to exit the Configuration Menu. The UPS Network 

Module is operational. 

4.

 

If your network is not configured with a DHCP server: 

a.

 

On the Main menu, enter 

2

 to display the Network 

Configuration submenu. 

b.

 

Enter 

2

 to modify the network settings. 

c.

 

Follow the on-screen instructions to enter the static IP 
parameters. A 

Done

 message appears when the 

parameters are saved. 

d.

 

Enter 

0

 to return to the Main menu. 

e.

 

Enter 

1

 to reset, and then enter 

2

 to restart the UPS 

Network Module with the new IP settings. 

 

Accessing the web interface 

  

 

CAUTION:

  It is highly recommended that browser access 

to the UPS Network Module is isolated from outside 

access using a firewall or isolated network. 

  

1.

 

On a network computer, launch a supported browser. The 
browser window appears. 

2.

 

In the Address field (Microsoft Internet Explorer) or the Location 
field (Mozilla and Firefox), enter: 

http://

xxx.xxx.xxx.xxx 

-or- 

https://

xxx.xxx.xxx.xxx 

where xxx.xxx.xxx.xxx is the static IP address of the UPS 
Network Module. The log in screen appears. 

3.

 

Enter the user name in the User Name field. The default user 
name is 

admin

4.

 

Enter the password in the Password field. The default password 
is 

admin

5.

 

Click 

Sign In.

 The HP UPS Network Module web interface 

appears. 

 

 

Configuring the UPS Network 

Module settings 

Use the Settings screens of the HP UPS Network Module web 
interface to configure the UPS Network Module. For more 

information, see the HP UPS Network Module User Guide on the HP 

website (http://www.hp.com/support/HPNM_Manuals). 

 

Technical characteristics 

    

Item 

Description 

Physical characteristics 

 

Dimensions (width x depth 

x height) 

132 x 66 x 42 mm (5.20 x 2.60 x 

1.65 in) 

Weight 

70 g (.15 lb) 

RoHS 

100% compatible 

Storage 

 

Storage temperature 
range 

-10°C to 70°C (14°F to 158°F) 

Ambient conditions 

 

Operating temperature 
range 

0°C to 40°C (32°F to 104°F) 

Relative humidity 

90% maximum, noncondensing 

Card performance 

 

Supply voltage 

5V ±5% 

Supply current (all LEDs 

on) 

300 mA maximum 

Functions 

 

Web supervision 

HTTP—5 browser windows maximum 
HTTPS—3 browser windows 

maximum 

Item 

Description 

Languages 

English or Japanese 

Alarms 

Email, SNMP trap, web interface 

Log 

400 measurements or events 

Server protection 

Up to 100 servers protected 

Network 

Fast ETHERNET, 10/100 Mb/s, 
autonegotiation 
HTTP 1.1, SNMP V1, SNMP V3, 

NTP, TFTP, SMTP, DHCP 

Identification 

User name and password 

Security 

SSL 3.0, TLS 1.0 

Browsers 

Microsoft® Internet Explorer 6.x or 

higher 

NMS 

HP Systems Insight Manager 

MIB 

Standard IETF UPS MIB (RFC 1628) 
HP Power MIB (cpqpower.mib) 

Settings (default values) 

 

IP network 

DHCP enabled 
IP address: 192.168.1.2 (manual 

configuration) 
Subnet mask: 255.255.0.0 
Gateway: 0.0.0.0 
NTP server: pool.ntp.org 

Web interface access 
control 

User name: admin 
Password: admin 

Configuration menu 
access control 

Password: admin (not modifiable) 

Date and time 

Synchronize with HP Power Protector 

Settings/AUX connector 

9600 bits/s, 8 bits, 1 bit stop, no 
parity 

 