Specifications 71
Fire alarm panel connections
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP
POD 40c G2.
Water specifications
The following table describes the chilled water system specifications for the HP POD 40c G2.
Feature
Specification
Facility input temperature to the HP POD
40c G2
12ºC to 24ºC (55ºF to 75ºF)
Working pressure
1,034 kPa (150 psi)
HP POD 40c G2 pressure drop
172.4 kPa (25 psi)
HP POD 40c G2 water flow rate
908.5 lpm (240 gpm)
Chilled water supply and return
connections
•
North America—Two 10.16 cm (4 in) ASME B16.5 class #150
flanges
•
International—Two DIN PN16 DN100 flanges
Rack specifications
Standard HP POD 40c G2 racks (AT978A)
Feature
Specification
U height
50U
Width
54.6 cm (21.5 in)
Depth
99 cm (39 in)*
Maximum load weight
1,360.7 kg (3,000 lb)
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
HP POD 40c G2 specification
Air temperature—Inlet to rack-mounted
components)
Dependent on IT configuration and chilled water inlet temperature
Chilled water temperature
12
°
C to 24
°
C (55
°
F to 75
°
F)
Total rack-mounted component air flow
Variable as required to maintain the hot aisle setpoint temperature
and dependent on IT configuration
Heat rejection capacity
600 kW
Environmental specifications
Feature
Specification
Operating temperature
-28ºC to 54ºC (-18ºF to 130ºF)