Specifications 104
Feature
Specification
Relative humidity
Operating: 5% to 95%; noncondensing
Non-operating: 5% to 95%; 38.7°C (101.7°F)
maximum wet bulb temperature with no cosmetic
damage
Operating altitude
Up to 1,000 m (3,300 ft) above sea level
Up to 2,000 m (6,600 ft) with 1% derating per + 100 m
(330 ft)
Transit altitude
UP to 15,000 m (49,000 ft) above sea level
Heat dissipation
1432 BTU/hr maximum at 100% rated load (High
Efficiency Mode)
4094 BTU/hr maximum at 100% rated load (Standard
Mode)
Audible noise
Less than 58 dBA at 1 meter typical (Normal Mode)
Less than 64 dBA at 1 meter typical (Battery Mode)
Leakage current
<3.5 mA
Surge suppression
ANSI C62.41 Category B3
Safety conformance 3 Phase UPS NA: UL 1778 4th edition; CSA C22.2,
No. 107.1 and No. 107.3
3 Phase UPS INTL: EN 60950-1 and IEC 62040-1-1
Agency Markings
3 Phase UPS NA: UL/cUL
3 Phase UPS INTL: CB, CE, GS, Ctick, GOST, BSMI
EMC (Class A)
3 Phase UPS NA: FCC Part 15, ICES
3 Phase UPS INTL: EN 62040-2
Battery specifications
Feature
Specification
Configuration
UPS internal batteries: (40) 12 V, 5 Ah
+1 ERM: (20) 12 V, 9 Ah
+2 ERMs: (40) 12 V, 9 Ah
+3 ERMs: (60) 12 V, 9 Ah
+4 ERMs: (80) 12 V, 9 Ah
Type
Each model contains maintenance-free, sealed,
valve-regulated lead-acid batteries.
Monitoring
Advanced monitoring for earlier failure detection and
warning
Charging
8-10 times the discharge time. Complete charge takes no
more than 48 hours. Approximately 5 hours to 80 percent
capacity at default nominal utility voltage and no load.
Battery runtimes
Battery runtimes are approximate and vary depending on the load configuration and battery charge.