HP 16A Скачать руководство пользователя страница 5

QuickSpecs

hp Modular Power Distribution Units

(Zero-U/1U Modular PDUs)

DA-11041

World Wide — Version 3 — December 11, 2002

5

A

D D I T I O N A L  

S

P E C I F I C A T I O N S

Low Voltage 24A

(NA/JPN/LA)

High Voltage 16A

(WW)

High Voltage 24A

(NA/JPN/LA)

High Voltage 32A

(INTL)

High Voltage 40A

(WW)

Part Number

252663-D71

252663-B24

252663-D72

252663-B31

252663-B21

Current

 (max)

24A

16A

24A

32A

40A

AC Voltage Range

100-127V

200-240V

200-240V

200-240V

200-240V

Frequency

 (Hertz)

50/60Hz

50/60Hz

50/60Hz

50/60Hz

50/60Hz

Load Capacity

 (VA)

2880 (@120V)

3680 (@230V)

4992 (@208V)

7360 (@230V

9200 (@230V)

Output Circuit
Breakers

4x15A

2X10A

4x15A

4x15A

4x15A

Overload Protection

Yes

Yes

Yes

Yes

Yes

Indicator Lights

Indicator light on each of the Extension Bars; and a main AC pilot light on the Control Unit

Plugs and Cables
Control Unit

 (x1)

Input:

 3.6m attached

cable with L5-30P

Output:

 Four IEC320-

C19 (12A ea)

Input:

 Detachable

input power cord
(country specific) with
a IEC 320-C20 inlet

Output:

 Two IEC320-

C19 (8A ea)

Input:

 3.6m attached

cable with L6-30P

Output:

 Four IEC320-

C19 (12A ea)

Input:

 3.6m attached

cable with IEC309-32A

Output:

 Four IEC320-

C19 (12A ea)

Input:

 Hardwire

Output:

 Four IEC320-

C19 (12A ea)

Note: Manual ON/Off control provided for each load group; switch guards provided to prevent inadvertent power Off.  The Control unit for the 16A model

has 2 outputs while the Control Unit for all other Modular PDUs has 4 outputs. The Extension Bars plug directly into the output-ends of the Control
Unit.

Extension Bars

 (x4)*

*Except for the 16A
model, which has 2
Extension Bars

Input:

 2m attached

cord with IEC320-C20

Output:

 Each Bar has

8 NEMA 5-15 outlets
(12A max per outlet,
12A max per Bar)

Input

: 2m attached

cord with IEC320- C20

Output

: Each Bar has

8 C13 outlets
(10A max per outlet,
12A max per Bar)

Input

: 2m attached

cord with IEC320- C20

Output

: Each Bar has

8 C13 outlets
(10A max per outlet,
12A max per Bar)

Input

: 2m attached

cord with IEC320- C20

Output

: Each Bar has

8 C13 outlets
(10A max per outlet,
12A max per Bar)

Input

: 2m attached

cord with IEC320- C20

Output:

 3 Bars each

with 8 C13 (10A max
per outlet, 12A max
per Bar); 1 Bar with 4
C19 (12A max per
outlet, 12A max per
Bar)

Содержание 16A

Страница 1: ... PDU Model s 200 240 VAC 16A Model mPDU 16A High 252663 B24 WW 24A Model mPDU 24A High 252663 D72 NA LA JPN 32A Model mPDU 32A High 252663 B31 INT L 40A Model mPDU 40A High 252663 B21 WW Feature List Single input power distribution units with a unique modular design architecture Up to 32 outlet receptacles Zero U 1U dense rack form factor Easily accessible outlet receptacles and improved cable man...

Страница 2: ... models come with an attached input power cord due to regulatory requirements for higher amperage devices And the 40A model has to be field wired Higher amperage mPDUs offer more outlets allow more equipment to be connected and are especially suited to the high density server deployments Small Form Factor and Flexible Mounting Options The Control Unit is zero U or 1U rack mountable And the Extensi...

Страница 3: ... out devices Current Ratings from 16A to 40A Modular PDUs are available in a wide range including four high volt models ranging from 16A to 40A current ratings and one low voltage 24A model Compatibility Ideal for use with the HP 9000 and 10000 Series Racks the Modular PDUs are largely designed for the dense rack environment These Modular PDUs connect directly to the facility input power In additi...

Страница 4: ...o 60 C Storage Relative Humidity 5 to 95 Storage Elevation 0 to 30 000 ft 0 to 9144 m Conformance Standards UL CUL CE NOM D 16A and 40A models UL CUL NOM 24A High and Low voltage models CE D 32A model Kit Contents 24 40A Modular PDUs ship with x1 Control Unit and x4 Extension Bars 16A Modular PDU ship with x1 Control Unit and x2 Extension Bars All models ship with 0U 1U Mounting brackets hardware ...

Страница 5: ...ea Input 3 6m attached cable with L6 30P Output Four IEC320 C19 12A ea Input 3 6m attached cable with IEC309 32A Output Four IEC320 C19 12A ea Input Hardwire Output Four IEC320 C19 12A ea Note Manual ON Off control provided for each load group switch guards provided to prevent inadvertent power Off The Control unit for the 16A model has 2 outputs while the Control Unit for all other Modular PDUs h...

Страница 6: ...Bars while all other 24 40A models ship with 4 Extension Bars 32 IEC 320 C 13 32 IEC 320 C 13 24 IEC 320 C 13 4 IEC 320 C 19 Applications Connects to low voltage models of the UPS R3000 XR and may also be connected directly into the facility input Connects to the high voltage models of the UPS R3000 XR and R6000 Note Except for the UPS R3000 XR North America high volt model where an additional cab...

Страница 7: ...uired on the PDU for connecting the RILOE cards Please refer to the Power Cord Matrix for more information on power cords cable part numbers input output descriptions ftp ftp compaq com pub products servers proliantstorage power protection powercordmatrix pdf 2002 Hewlett Packard Company Hewlett Packard the Hewlett Packard logo CarePaq ProLiant and StorageWorks are trademarks of Hewlett Packard Co...

Отзывы: