HMI

 HOYME MANUFACTURING INC.              PH. 1-800-661-7382 

 

 

           www.hoyme.com  

SCHEMATIC WIRE DIAGRAM OF 

ADAPTOR ADP- 0241-10A 

 

 
Note: This marking is also on the cover of the 
Adaptor unit as well as on a label to be placed 
next to the wiring diagram of the appliance.  
 
This Adaptor uses a 24Vac Coil SPDT to 
develop a 10A capacity for 120Vac if needed 
and a 24Vac Coil DPDT to develop multiple 
contact points for 24Vac. Coils are connected  
in parallel and therefore act as one relay.  

 
Schematic Wire Diagram ADP-0241-10A 
Activated by a Manual or Automatic Switch   
to Control a Furnace Fan a 120Vac i.e.  
Booster Fan and a Fresh Air Inlet Damper.  

Damper remains closed during furnace firing. 
(See 

‘Notes’

 for alternatives) 

 

Schematic Wire Diagram of ADP-0241-10A 
Activated by an Exhaust Fan Auxiliary Relay 
Switch and/or Thermostat Controlling a 
Furnace Fan, and a 

Power Close Fresh Air 

Damper with Relay

  . 

Damper also opens during furnace firing.

 

 

 

Suggestion:

 

Use Fresh Air 

Damper with Relay

   

HAC – 0

X

1

1

 – O

PC

 where 

X

 = Diameter of Damper,  

1

 = Relay, 

PC

 = 

P

ower 

C

lose 

       

Note:

 For PC damper only, a toggle switch in 

series with 24Vac electrical supply line to the 
Damper will cause it to open as required.  
 

* Note:

 For 

PC damper without relay

 and if 

adding a Combustion Air Damper, re-connect 
Fresh Air Damper from furnace ‘C’ to Green 
wire of the Combustion Air Damper. Both 
dampers will open during firing of the furnace. 
  

* Note: 

If existing ventilation relay (auxiliary 

relay switch) cannot be located, relay wires 
presently connected to ‘R’ and ‘G’ of the furnace 
are to be re-connected to 

#3

 of ADP and ‘C’ of 

the furnace.  ADP 

#6

(G

F)

 is then to be 

connected to ‘G’ of the furnace and Thermostat 
wire ‘G’ is to be connected to 

#7

(G

T)

 of the 

Adaptor.    