background image

10 

 

Calibration test for pulley/ internal rotation guard   STP in the display no 5?? 

For example needed if received an E01 error/ alarm 

 

If drive equipment is wired by us from factory and mounted in a RHE this test have been done before delivery 

 

Before opening DRHX

, the mains voltage must be 

disconnected for at least 3 minutes

 

to ensure that there  

Is no risk of dangerous residual currents in electronic circuits or capacitors. 

 

The test button you find to the right of the DIP switches, see figure 15.2 on page 7.  

 

1.  Turn off the DRHX controller and 

remove the belt from the pulley.

  

 

2.  Power up the DRHX controller and 

briefly press

 the test button, < 1 second, to start test mode 

The LED will shine orange. Display will show "tSt" for test mode. 

 

3.  Wait for the stepper motor to reach maximum speed. It's limited to 100 rpm in this test.  

 

4.  After the stepper motor has reached the maximum speed, the system will start performing the internal rotor 

guard function. The stepper motor will accelerate at short intervals every 10 seconds (that should be 
possible to hear) for a minute.  

 

5.  If the stepper motor stops and restarts after one minute the internal rotor guard is correctly calibrated.  

 

6. 

Press the test button for 2 seconds to end test mode

. LED turn green. See point 8. 

 

7.  If the stepper motor continues to run for more than one minute, a recalibration needs to be done: 

 

Recalibration

:  

Press and keep pressing the test button 

until LED flashes orange 

( can take 10

–50 sec).  

 

Remove your finger from the button and the LED will turn green, the pulley/ internal rotor guard has been 
calibrated. 
 

 

8.  After, turn off the DRHX controller and mount the belt. Start normal operation procedure. 

 

Alarms and fault codes

 

see table 19, page 10 and 19.1 page 11

 

 

DRHX has a built-in alarm monitor, which monitors optimal fault-free operation and triggers an alarm if operating  
or performance problems are observed. Alarm codes can be read on the display. 

Alarms are either ”Critical” or ”Non-

critical” alarms: ”Critical” alarms stop the stepper motor. ”Non-critical” alarms reduce stepper motor performance.  

 

 

The built-in alarm monitor stops the DRHX. 

 

 

If the alarm situation passes, the alarm is automatically reset and DRHX will be restarted.  

 

 

If the maximum number of restarts (5 times/ 1 h) is overstepped, the 

alarm must be reset 

 

 

 

Alarm reset

The alarm is automatically reset if the power is disconnected for longer than 60 seconds.  

or faul codes and alarm overview etc see table 19 and 19.1 in page 11 
 

 

 

 

 

 

 

 

 

 

 

 

 

Remarks:  

"C" = Critical alarm, stop the motor. / "NC" = Non-critical , reduce the motor performance. 
”RP” = Reducing performance.  
”SA5 ”= Stepper motor stops after 5 restarts caused by same fault within 60 min.  
”S” = Stepper motor stops immediately 

Содержание DRHX-1055 MAD5

Страница 1: ...efore connecting mains voltage to the DRHX controller all components i e stepper motor belt pulley and rotor must be installed correctly all openings covers and cable glands must be properly fitted and closed To maintain the specified enclosure rating unused cable glands should be replaced with blank glands plug Controller DRHX contains capacitors which become charged during operation These capaci...

Страница 2: ...m 50Hz 150 170 200 400 rpm Voltage Input 50 60Hz V 1x230 1x230 1x230 Motor voltage V 3x0 200 V AC 3x0 200 V AC 3x0 200 V AC Motor power kW 0 055 0 110 0 220 Rated current A 0 6 2 4 2 4 Class of protection IP54 IP54 IP54 Weight motor kg 2 4 3 5 5 Weight controller kg 0 9 0 9 0 9 Shaft Ø motor mm 12 12 12 8 Nm torque at max 250 motor rpm but only max 5 Nm torque at max 400 motor rpm 6 ...

Страница 3: ... to avoid false alarms and errors it is important to install it proper The stepper motor comes with four holes for attachment to a solid mounting plate The mounting plate must be firmly attached to the chassis of the rotary heat exchanger or AHU see figure 12 2 1 marked 1 Do not use vibration dampers or springs Must be mounted on a fixed motor bracket ELECTRICAL INSTALLATION Potential equalization...

Страница 4: ...pushing the wire into the terminal without using tools Alternatively the terminal spring can be loosened by pressing it lightly with a screwdriver or similar implement See fig 13 9 Stripped wire ends or end sleeves must be between 8 and 10 mm Wires can be removed by carefully loosening the terminal spring by pressing lightly with a screwdriver or similar implement See fig 13 9 Cable entries cable ...

Страница 5: ...the connector from the cable from the DRHX extension cable The connector can be separated again by releasing the locking pawl on both sides of the connector on the motor cable and pulling the 2 connectors apart The extension cable should be connected to the terminals marked U Brown V Black W Blue PE Yellow Green If rotation of rotor is wrong switch the V black and W blue cable to change motor dire...

Страница 6: ...changer from Hoval The DRHX series is equipped with 4 DIP switches for setting e g the stepper motor size and maximum motor speed DIP 1 2 motor size DIP 3 4 motor rpm see table 15 1 1 and 15 1 2 Required motor rpm is calculated by Hoval Depends on rotor Ø pulley Ø rotor and motor torque and given rotor rpm See table 15 1 3 Table 15 1 3 ...

Страница 7: ... long the button is pressed in Running Test for RHE Belt should be mounted on rotor and pulley Start the test by pressing and continuously holding the test button The controller will enter test mode Visible in display and LED will be orange The test will remain active until the test button is released During this test run the motor will rotate with a maximum speed of 100 rpm Stop the test by relea...

Страница 8: ...ies of rotor monitoring systems internal and external The factory setting is Internal rotor guard external is an option Hoval option RG3 Internal rotor guard The internal rotor guard monitors the rotation of the rotor by measuring the electronical signal returning from the motor will take place every 10 seconds After five consecutive failed detections within 1 hour the alarm E01 is given see page ...

Страница 9: ...g signal Built in protection If the temperature inside DRHX overstep 95 C DRHX will attempt to reduce its internal heat generation by reducing the amount of current that is sent to the stepper motor DRHX has built in current limitation for the protection of stepper motor and cables and can therefore not supply more current than it is rated to see technical data page 2 DRHX is short circuit protect...

Страница 10: ...turn green See point 8 7 If the stepper motor continues to run for more than one minute a recalibration needs to be done Recalibration Press and keep pressing the test button until LED flashes orange can take 10 50 sec Remove your finger from the button and the LED will turn green the pulley internal rotor guard has been calibrated 8 After turn off the DRHX controller and mount the belt Start norm...

Страница 11: ...st page 10 Make the test calibration again see page 10 If the motor is too powerful for the rotors load large motor to a very small load The rotor torque is lower than the internal rotor guards minimal torque limit for chosen type of DRHX MRHX system i e spare part for old RHE Exchange type of MRHX motor and if needed DRHX controller so its fits the rotor type Contact Hoval for support E06 Wobblin...

Страница 12: ...at the DRHX has a signal connected to the Start Stop input digital input Din 1 2 or 3 depending on the configuration Lacking 0 10 V DC control signal Check that DRHX receives an operating signal 1 1 V on 0 10 V In Active alarm Read active alarms via the display and remove what is causing the alarm see page 11 can also be read by using DRHX PC Tool or via Modbus The stepper motor has been stopped 5...

Отзывы: