6 Alarms and monitoring
The system monitors itself. All the alarms are registered in the alarm list and displayed by TempTronic RC. Priority A alarms
are also displayed via the collective trouble indicator.
Alarm
Priority Cause
System reaction
Benefit
Gas burner
A
There is a burner malfunction.
The affected unit switches to operating
mode 'Off'.
prevents damage to the
burner
Fresh air
damper
A
The fresh air/recirculation air damper is
jammed or its actuator is defective.
The affected unit switches to operating
mode 'Off'.
Avoids loss of energy /
undefined states of
operation.
Filter
B
The pressure difference for filter monitoring
was exceeded for more than 5 minutes.
–
Informs the user of the
necessity of maintenance
work
Isolation
B
The isolation switch on the unit has been in
the 'Off' position for more than 30 minutes.
–
Avoids unintentional
switching off.
Supply air
sensor
B
The supply air sensor is defective.
The plant operates with the minimum heat
output until the fault is eliminated.
Avoids interruptions of
plant operation.
Fan
A
A fan motor has overheated.
The affected unit switches to operating
mode 'Off'.
Avoids damage to the fan
motor.
70
Control system
Alarms and monitoring
Содержание DGV-6/30
Страница 2: ......
Страница 4: ...2...
Страница 5: ...Safety A 1 Symbols 4 2 Operational safety 4 3 Information for a user manual 4 3 Safety Content...
Страница 20: ...18...
Страница 34: ...32...
Страница 76: ...74...
Страница 77: ...Operation I 1 Operation 76 2 Maintenance and repair 77 3 Dismantling 78 4 Disposal 78 75 Operation Content...
Страница 81: ......