8
4 210 803 / 00
2.3 Hot water output at heating flow 60 °C
2.3.1 MultiVal CSRR (540-2000)
Hot water output
MultiVal
Loading pump Biral
1
dm
3
/10 min.
4
dm
3
/h
5
Type
m
3
/h
2
mbar
3
Type
mWS
Type
mWS
45 °C
45 °C
55 °C
kW
6
flats
7
CSRR (540)
1.5
18
AX 13
3.2
MX 12
2.4
481
230
179
9.4
2
CSRR (540)
2.5
62
AX 13
2.2
MX 13
2.9
497
324
252
13.2
2
CSRR (630)
1.5
18
AX 13
3.2
MX 12
2.4
552
230
179
9.4
2
CSRR (630)
2.5
62
AX 13
2.2
MX 13
2.9
568
324
252
13.2
2
CSRR (630)
3.0
81
A 13
2.7
MX 13
2.2
589
454
353
18.5
3
CSRR (800)
2.5
62
AX 13
2.2
MX 13
3
710
324
252
13.2
3
CSRR (800)
3.5
110
A 13
2.2
MX 13
1.8
734
474
368
19.3
3
CSRR (1000)
3.5
110
A 13
2.2
MX 13
1.8
908
474
368
19.3
4
CSRR (1000)
4.5
243
A 14
3
M 14
3.5
938
658
512
26.8
5
CSRR (1250)
4.5
243
A 14
3
M 14
3.5
1105
658
512
26.8
5
CSRR (1500)
5.5
151
A 14
2.3
M 14
2.3
1442
791
615
32.2
7
CSRR (2000)
5.5
151
A 14
2.3
M 14
2.3
1860
791
615
32.2
8
1
Biral loading pump
= Combined with heat pumps
2
m
3
/h
= Volume flow of the loading pump (60 °C)
3
mbar
= Heating-side flow resistance in the heating battery
4
dm
3
/10 min
.
= Hot water peak performance in 10 minutes. Calorifier heated up to 60 °C (according Procal test rules)
5
dm
3
/h
= Continuous output per hour. Cold water temperature 10 °C (according Procal test rules)
6
kW
= max. heat pump capacity for heating battery
7
flats
= Power characteristic number in accordance with DIN 4708 = number of flats, which can be supplied
with hot water if the water heater is heated with the boiler and is permanently after-heated
(Standard flat: 1 bath - 4 rooms - 3,5 persons)
Technical Data