82
4 214 153 / 00
MAINTENANCE
2. Extend the regulator unit upwards approx. 20 cm (Fig.
08) and move it up and down firmly several times (ap
-
prox. 10…20 cm).
3. Put the regulator unit correctly back in position!
4. Clean the impeller (4) of the induced-draught fan
using a brush and vacuum cleaner; use a scraper to
remove any encrusted deposits.
5.
Vacuum the entire flue gas collector.
4
Fig. 08
6. Lubricate the following components (Fig. 09) with ad-
hesive lubricating grease:
- Guide rails (A)
- Lever-shaping pipe contact points (B)
- Lever rotation points (C)
- Eccentric disc (D)
7.
Refit the flue gas collector cover so that it is sealed!
A
C
B
D
B
A
C
Fig. 09
8.2.3 Cleaning flue gas sensors
1. Remove the rear casing panels.
2. Remove the lambda probe (2, Fig. 10) and clean
using a brush and vacuum cleaner.
3.
Remove flue gas temperature sensor with immersion
sleeve and clean.
2
Fig. 10
8.2.4 Clean and inspect the post-combustion ring
and dust separator
B
C
A
Fig. 11
A Dust separator
B Post-combustion ring
C Burner
1.
Remove the burner cover after first releasing the self-
tapping screw on the back of the pellet hopper.
2. Dismantle the secondary air connection (1, Fig. 12)
(release screws and remove).
1
Fig. 12