4 215 983 / 01
22
MaInTEnanCE (OnLy FOR BOILER COnTROLLER WITH TOpTROnIC® E COnTROL)
6.2
Cleaning
Insufficient cleaning not only leads to increased fuel con-
sumption, it also shortens the operating time of the boiler.
!
CAUTION
The boiler must be cleaned at least 1 x per
year by a chimney sweep.
(Observe local regulations).
• Disconnect the heat generator from the mains (main
switch, fuse).
• Unscrew the hexagon locking nuts with holes with the
sup plied steel spike (Figure 02).
!
CAUTION
The locking nuts without holes must under no
circumstances be loosened. Otherwise the
door panel can detach from the boiler.
• Tilt out the boiler door with boiler.
• Thoroughly clean the combustion chamber (2), second
compartment (3) and third compartment (4) with a brush
or by spraying.
• Remove the cleaning cover (5, Figure 03) behind on the
flue gas collector. Remove residues from the collector.
Brush the boiler rear wall and the space between the
pipe ends clean.
•
Empty the flue gas collector at the outlet (6) during wet
cleaning.
• Sal the cleaning openings tight.
• Close the boiler doors and tighten screws.
• Insert burner connection plug and switch the boiler
back on.
6.3
Lubrication of the seal and thread
6.3.1 Lubrication of the seal
Reversing chamber
Combustion chamber
Cleaning opening (flue gas collector)
6.3.2 Lubrication of the thread
Hinged flange bottom/top
Cleaning opening (flue gas collector)
During long operating breaks,
preserve the boiler.
Figure 02
Figure 03
6
5
Figure 04
4
3
2
Содержание 2-Max-3 condens