5. Plan the job and obtain the needed materials. For electrical you may need 
Romex or you may be required to used wire in conduit or other option depending 
on your situation and local code. You may need conduit, PVC or other pipe for the 
outdoor connections. 

For water lines we suggest ¾ PEX.  If your run is over 100 ft. one-way it is possible 
to exceed this maximum distance by using 1” PEX after performing a pump head 
calculation and consulting the pump curve. 

If you are at this point and are not sure how to proceed, you are probably not a 
good candidate to perform these tasks. 

6. Mount the indoor unit on the wall for placement purposes.  Make sure it is 
level. 

7. Unpack the line-set and place one end of it near the connection to the indoor 
unit and place the other end near the outdoor unit. Connect the line-set to the 
indoor unit. Do not other end.  If the line-set is not long enough and you did not 
order a 25 ft. extension, your HVAC technician can make one easily if he knows in 
advance that he will need to do so. Same applies to the control cable that 
connects the indoor unit to the outdoor unit. Make a watertight professional 3” 
exterior wall penetration.  Fit the line-set and control cable through the hole and 
carefully bend it towards the outdoor unit. Do this work neatly and carefully, 
considering the requirements of the drain tube. Use tape to wrap the line-set and 
control cable.  Use the included grommet to seal the hole. Secure the line-set to a 
wall or other structure so it cannot move in the wind, first making sure you have 
enough extra line at each end for your connections. Know what kind of structural 
and finish materials you are working with  and obtain the correct hardware to 
properly attach the line-set to the structure. Measure twice! Make sure your line-
set and cables are long enough.

8. Before starting installation of the water connections, inspect the water heater 
for leaks, corrosion or other problems.  If the water heater needs to be changed 
out, now is the right time.  If the existing water  heater is acceptable, proceed 
with the following installation.

Содержание ACWH18

Страница 1: ...performed similar work previously and who has the required tools and equipment It is up to the user to determine if a permit is needed and to determine what self installation work is allowed under loc...

Страница 2: ...condensate drain tube 2 Determine a proper location for the outdoor unit and set a pad in place Pre fabricated pads for air conditioners are available from Lowes or Home Depot or similar retailers Al...

Страница 3: ...ician can make one easily if he knows in advance that he will need to do so Same applies to the control cable that connects the indoor unit to the outdoor unit Make a watertight professional 3 exterio...

Страница 4: ...ker panel If it s a gas fired water heater close off the gas valve found ahead of the water heater burner and controls If gas be sure you know how to turn the gas on and off including resetting the ig...

Страница 5: ...xisting Tank Fig 3 Tank Tap w Pre heat Tank The Tank Tap options in Figs 2 3 avoid interrupting the cold water supply line and adding a Tee Using the Tank Tap Adapter avoids the need for a permit in m...

Страница 6: ...sediment issues NOTES Do not return the ACWH unit s hot water by placing a Tee in the hot water delivery pipe above the water heater This approach will allow water to pass from the ACWH unit directly...

Страница 7: ...t Make sure that the water line from the water heater s cold water supply tee is connected to the cold water in stub on the ACWH unit Performance is significantly impaired if the water line connection...

Страница 8: ...water faucet Note the water will be cool because the tank has recently been drained 6 Turn the power or gas back on the water heater and check for normal operation NOTE The ACWH unit is capable of gen...

Страница 9: ...Unique Design Utilizes existing Boiler or Water Heater Drain for Inlet and Outlet of HotSpot Unit No need to turn off water to property for installation No permit needed for installation in most areas...

Страница 10: ...old drain valve may be thrown away With a sharpie make 2 alignment marks on the inner pipe Make the second alignment mark here Bend the pipe so it will point up with the first alignment marks Use a p...

Страница 11: ...ecure the inner pipe s position The inner pipe inside the tank should be pointing strait up Double check the second alignment mark through the drain fitting Once the union nut is tight tape the thread...

Страница 12: ...since 1970 The PEX we refer to is PEX Tube standard CTS OD and we recommend use of diameter It can be purchased online or through hardware stores like Lowes or Home Depot You will need to have the co...