Page 9

UP 15-42F/FR

Closed Systems, 60 Hz

UP 26-64F

Closed Systems, 60 Hz

SECTION III: PRE-INSTALLATION (cont.)

Figure 4: 

GRUNDFOS UP 15-42F performance curve

Figure 5: 

GRUNDFOS UP 26-64F performance curve

Note:

Zone valves on the heat source supply to the indirect heater are not recommended 

and will drastically reduce performance.

System performance can also vary based on the heating capacity of the boiler.  If the
minimum coil output (assume coil output = boiler output) listed in Tables 2 and 3 is not met,
the output (first hour rating) of the water heater will not be met at the selected flow rate.  
To approximate the reduction in first hour rating as a result of low boiler capacity, use the
following formula:

New first hour rating = (First hour rating) * (Actual boiler output)/(Minimum coil output)

For example, the first hour rating of a 50SK at a 77°F rise with an 8 GPM heat source flow rate
using a boiler having a DOE heating capacity (output) of 60,000 BTU/Hr would be:

New first hour rating = (160 gal) * (60,000 BTU/Hr)/(77,000 BTU/Hr) = 125 gal

Содержание HL119SK

Страница 1: ...that commonly reduces the life of other in direct water heaters 3 Steel coil increases heat transfer for faster recov ery and the luxury of never running out of hot water 3 Coils and tank lining are...

Страница 2: ...rvice This unit must be installed by licensed or authorized installers or technical personnel that service water heating equipment The heater must be installed in accordance with all local codes and o...

Страница 3: ...Section I Specifications 4 Section II General Information 6 Section III Pre Installation 8 Section IV Installation 10 Section V Maintenance 13 Section VI Troubleshooting 14 Section VII Parts List 15...

Страница 4: ...etting for normal residential use is 120 F ECR recommends a tempering valve or anti scald valve be installed and used according to the manufacturer s directions to prevent scalding HL30SK 22 35 3 4 27...

Страница 5: ...78 88 000 190 96 000 202 104 000 214 111 000 HL80SK 188 76 000 212 91 000 224 98 000 221 97 000 233 104 000 245 112 000 257 119 000 HL119SK 220 76 000 244 91 000 256 98 000 253 97 000 265 104 000 277...

Страница 6: ...provides limited control for domestic hot water temperature The proper temperature setting for domestic hot water use is 120 F 49 C If hotter water is required a tempering device or anti scald device...

Страница 7: ...r system When hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at...

Страница 8: ...th 180 F and 200 F boiler water To determine the appropriate circulator for your system follow these three steps 1 Calculate the pressure drop of all straight pipe and fittings on the supply and retur...

Страница 9: ...inimum coil output assume coil output boiler output listed in Tables 2 and 3 is not met the output first hour rating of the water heater will not be met at the selected flow rate To approximate the re...

Страница 10: ...be minimized A flow check valve must be installed on the return line All piping to the inlet cold and outlet hot domestic water connections should be new copper with a minimum size of 1 2 ID for model...

Страница 11: ...IV INSTALLATION cont CHECK VALVES ZONE CIRCULATORS ISOLATION VALVES ADDITIONAL ZONES INDIRECT CIRCULATOR INDIRECT WATER HEATER TO HEATING ZONE AIR SEPARATOR AIR VENT EXPANSION TANK COLD WATER INLET BO...

Страница 12: ...the indirect calls for heat the indirect coil tank heater circulator must start rather than opening a zone valve the system circulator stays off and the boiler must light to reach high limit WIRING NO...

Страница 13: ...nd at least yearly once a time interval for inspection has been developed It is recommended to check the rod s six months after the heater is installed If the anode rod had reduced in size by two thir...

Страница 14: ...k power supply Replace as necessary Faulty tank aquastat Replace aquastat Boiler cycles more than 5 times per day during hotest months Excessive demand Reduce demand or consider larger tank Faulty aqu...

Страница 15: ...HL50SK 3 HL80SK 3 HL119SK 5 Leak Detector Fitting HL30SK HL40SK 5 Leak Detector Fitting HL50SK HL80SK HL119SK 6 ST00601 1 T P Relief Valve 3 4 LL100XL HL30SK HL40SK HL50SK 6 ST01001 1 T P Relief Valve...

Страница 16: ...e unauthorized alteration improper repair or maintenance excessive pressure or leaks at water connections or any other similar cause 5 The failure or malfunction results from failure to keep the unit...