24
3) Drain Timer
The Drain Timer is factory-adjusted, and no adjustment is required.
SETTING
TIME
Dip Switch
Dip Switch
No. 3
No. 4
T1
T2
OFF
OFF
10 seconds
150 seconds
ON
OFF
10 seconds
180 seconds
OFF
ON
10 seconds
120 seconds
ON
ON
20 seconds
180 seconds
T1: Time to drain the Water Tank
T2: Time to restrain defrost completion
4) Drain Counter
CAUTION
Do not adjust the Drain Counter, or the Evaporator may freeze up.
The Drain Counter is factory-adjusted to drain the Water Tank every 10 cycles, and no
adjustment is required. However, where water quality is bad and the icemaker needs a
pump drain more often, the Drain Counter can be adjusted as shown in the table below:
SETTING
FREQUENCY
Dip Switch
Dip Switch
No. 5
No. 6
OFF
OFF
every cycle
ON
OFF
every 2 cycles
OFF
ON
every 5 cycles
ON
ON
every 10 cycles
Содержание KM-900MAF
Страница 6: ...6 2 KM 900MWF We reserve the right to make changes in specifications and design without prior notice ...
Страница 7: ...7 3 KM 900MRF We reserve the right to make changes in specifications and design without prior notice ...
Страница 8: ...8 4 KM 900MRF3 We reserve the right to make changes in specifications and design without prior notice ...
Страница 9: ...9 5 CONDENSING UNIT URC 12F ...
Страница 11: ...11 II GENERAL INFORMATION 1 CONSTRUCTION a KM 900MAF ...
Страница 12: ...12 b KM 900MWF ...
Страница 13: ...13 c KM 900MRF ...
Страница 14: ...14 d KM 900MRF3 ...
Страница 27: ...27 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM 900MAF ...
Страница 28: ...28 b KM 900MWF ...
Страница 29: ...29 c KM 900MRF and KM 900MRF3 ...
Страница 30: ...30 2 WIRING DIAGRAMS a KM 900MAF Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 ...
Страница 31: ...31 b KM 900MWF Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 ...
Страница 32: ...32 c KM 900MRF Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 ...
Страница 33: ...33 d KM 900MRF3 Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 ...