3. Controls and Adjustments
CAUTION
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
HOSHIZAKI Technical Support at 1-800-233-1940.
a) Default S4 Dip Switch Settings
The dip switches are factory-adjusted to the following positions:
Dip Switch No. 1
2
3
4
5
6
7
8
9
10
KM-515MAH
OFF OFF OFF OFF OFF OFF OFF OFF ON OFF
KM-515MWH OFF OFF OFF OFF OFF OFF OFF OFF ON OFF
KM-515MRH OFF OFF OFF OFF OFF OFF OFF OFF ON OFF
Freeze Timer (9 & 10)
Pump-Out Frequency Control (5 & 6)
Do Not Adjust
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
Normally off (7 & 8)
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer is only active during the initial harvest cycle. Every cycle thereafter the
pump-out timer's harvest timer (S4 dip switch 3 & 4, T2) acts in place of the harvest timer
on KM‑515M_H models, as the pump out occurs every cycle. See "II.C.3.c) Pump Out
Timer (S4 dip switch 3 & 4)."
Dip Switch Setting
Time
(seconds)
No. 1
No. 2
OFF
OFF
60
ON
OFF
90
OFF
ON
120
ON
ON
180