8)
Shutdown
a) Thermostatic Bin Control: KM-1301SAH-E
When the unit is running hold ice in contact with the thermostatic bulb, the
thermostatic BC switch opens within 10 seconds, shutting down the unit (CB
red "POWER OK" LED is off). The bin control is factory set, and generally
no adjustment is required. However, adjustment may be needed in some
conditions, particularly at higher altitude locations.
Diagnosis:
See "IV.C.1.
Thermostatic Bin Control Check."
b) Mechanical Bin Control: KM-1301SWH-E, KM-1301SRH-E
See "IV.C.2.a) Mechanical Bin Control Check."
Legend:
BC
–bin control;
CB
–control board;
Comp
–compressor;
FM
–fan motor;
FMR
–fan
motor-remote;
F/S
–float switch;
HGV
–hot gas valve;
HM
–headmaster (C.P.R.);
LLV
–liquid line valve;
PM
–pump motor;
TXV
–thermostatic expansion valve;
WV
–inlet water valve