PROBLEM
POSSIBLE CAUSE
REMEDY
e) Compressor
1. Loose connections.
1. Tighten.
2. Motor winding opened
or grounded.
2. Replace.
3. Motor Protector
tripped.
3. Find out the cause of
overheat or overcurrent.
f) Power Supply
1. Circuit Ampacity too
low.
1. Install a larger-sized
conductor.
[6] Gear Motor and
Compressor start, but
no ice is produced
a) Refrigerant Line
1. Gas Leaks
1. Check for leaks with a
leak detector. Reweld
leak, replace drier and
charge with refrigerant.
The amount of refrigereant
is marked on Nameplate
or Label.
2. Refrigerant line
clogged.
2. Replace the clogged
component.