Instructions for Use
ComPass B 4023841-001
Electrical connection
4.4.
Terminal strips
4.4.1.
The terminal strips are located in the rear wall of the instrument. If provided on the side of the
switchgear, perform electrical connection according to the following terminal reference list (See also
circuit diagram on the top side of the instrument, numerical arrangement from right to left). Use fer-
rules of L=6 mm, max. 0.75 mm2 .The maximum permissible tightening torque is 0.4 Nm.
Assignment of terminal strips
4.4.2.
Circuit diagram on top side of the instrument
Figure 20:
CT/Digital I/O/Supply Voltage
Terminal No
Designation
Assignment
Direction
1
I1 br
CT Phase 1 (brown)
Input
2
I1 bl
CT Phase 1 (blue)
Input
3
I2 br
CT Phase 2 (brown)
Input
4
I2 bl
CT Phase 2 (blue)
Input
5
I3 br
CT Phase 3 (brown)
Input
6
I3 bl
CT Phase 3 (blue)
Input
7
Earth
Input/Output
8
Input
External input
Input
9
Input
External input
Input
10
K1
Relay 1
Output
11
K2
Relay 2
Output
12
K3
Relay 3
Output
13
K4
Relay 4
Output
14
|
Common contact for all relays
Output
15
24-230 V ~/+
24-230 V AC/DC ~/+
Input
16
24-230 V ~/-
24-230 V AC/DC ~/-
Input
Terminal assignment of CT/Digital I/O/Supply Voltage
Table 2:
14
Dipl.-Ing. H. Horstmann GmbH