Firmware Update for XLE, XLEe (Gen. 2) 

 

a.

  Establish communication between Cscape and the controller using a direct serial connection to MJ1 or 

USB. 

b.

  Make sure your application is available on your PC or upload the application. 

c.

  Make sure the machinery connected to the OCS is in a safe state for firmware update. 

d.

  Start the firmware update by selecting 

File 

 Firmware Update Wizard

e.

  The correct product type should be selected, if it is not select the type of controller from the drop-down 

list. 

f.

  Press the Start button. 

g.

  Wait for the firmware update to complete. 

h.

  If there is a communication failure check the cable, connections and comm. port setting and try again. 

i.

  Firmware updates typically delete the user applications to ensure compatibility.  You will need to reload 

your application. 

j.

  Test the operation of the equipment with the new firmware before returning the OCS system to an 

operation mode. 

 

 

Firmware Update for the XLE/ XLEe (Legacy)

 

Update

 

firmware in an XLE (Legacy) by completing the following steps: 

 

a.  Connect to the MJ1/Port 1 programming port with Cscape software. 

b.  Run the executable file downloaded from the Horner website (Step One), which will place firmware files in default 

folder locations. 

c.  In Cscape open a new or existing project .csp file, click 

File

 

 

Firmware Update Wizard

.  

d.  In 

Firmware Update Wizard

, verify that the product type matches the connected device. Then select the 

appropriate CAN network option. The default option is CsCAN; if unsure, leave as default. Click 

Ok

.  

e.  You may receive a Warning window referring to firmware updates using high-speed communications. Click 

Ok

.  

f.  In the 

Firmware Update

 window, click 

Start

.  

g.  Once the download has completed, click 

Close

. Click 

Ok

 in the Update Complete window.  

h.  Verify in 

View Status

 in the 

System Menu

 that the desired firmware has been loaded.  

 