3.

 

INSTALLATION 

Observe the following procedure to install the option module:

 

1. 

Disconnect all connectors from the X-Series unit including  power. 

2. 

Remove the four screws on the back of the X-Series unit and remove the back cover.  The back cover will be replaced with the extended back cover 
that ships with the I/O add-on.  Screws are re-used (Figure 1). 

3. 

Plug the HSQ module onto the 24-pin connector.  Ensure that all the pins are properly aligned (Figure 2). 

4. 

Place the extended back cover onto the unit.  It can be helpful to tip it at an angle so the connector on the module passes through the opening in the 
back cover. 

5. 

Place the screws back into the hole and turn the screw slowly counter clockwise until it clicks into the threads.  This prevents the screw from being 
cross-threaded.  Turn the screw clock-wise until the cover is firmly secured.  Repeat this process for all four (4) screws.  Do not tighten the screws to 
more than 0.4Nm 

NOTE:

 When using this module with an HE-XE104, HE-XE105, or similar XL models with a 13 pin bottom I/O connector, the add-on module connector 

interferes with the stock I/O board connector.  It is necessary to order a replacement I/O connector available as part number HE-XKIT45.  This is not necessary 
for the 102 and 103 style XL units. 

 

 

 

 

 

 

 

 

 

 

 

Note: XLE used as an example, the procedure is applicable to all XL-Series 

 

4.

 

INSTALLATION / SAFETY 

When found on the product, the following symbols specify:

 

 

WARNING:

 To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections. 

WARNING:

  To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible. 

WARNING:

  Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.  

WARNING:

 In the event of repeated failure, do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse.  

WARNING:

 Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment.   Read and 

understand this manual and other    applicable    manuals    in    their    entirety    before proceeding.  Failure to observe this precaution could result in severe bodily injury or loss of life. 

All applicable codes and standards must be followed during the installation of this product. Adhere  to  the  following  safety  precautions  whenever  any type of connection is made to the module: 

 

Connect  the  safety  (earth)  ground  on  the  power connector first before making any 
other connections. 

 

When  connecting  to  electric  circuits  or  pulse-initiating equipment, open their related 
breakers. 

 

Do not make connections to live power lines. 

 

Make  connections  to  the  module  first;  then  connect  to the circuit to be monitored. 

 

Route power wires in a safe manner in accordance with good practice and local codes. 
 

 

Wear  proper  personal  protective  equipment  including safety  glasses  and  insulated 
gloves  when  making connections to power circuits. 

 

Ensure hands, shoes, and floors   a r e   dry before  making any connection to a power 
line. 

 

Make  sure  the  unit  is  turned  OFF  before  making connection to terminals. 

 

Make  sure  all circuits  are  de-energized  before  making connections. 

 

Before each use, inspect all cables for breaks or cracks in the insulation.  Replace 
immediately if defective

5. 

TECHNICAL SUPPORT

 

For assistance and manual updates, contact Technical Support at the following locations: 
 

NORTH AMERICA 

(P) 317-916-4274, (F) 317-639-4279 
Web: 

http://www.heapg.com

 

Email

[email protected]

 

EUROPE

 

(P) +353-21-4321266, (F) +353-21-4321826 
Web: 

http://www.horner-apg.com

 

Email

[email protected]

 

Warning:

  Electrical Shock Hazard. 

Warning:

  Consult user documentation. 

Отзывы: