3)
Ensure the proper wiring is used for each of the 3 pins
A
,
B
, and
C
on the Universal Analog
Inputs as seen in the reference image below:
Figure 8.9
–
Wiring Details
Wiring Details
:
SPRING CLAMP TERMINALS: Solid/Stranded wire
—
16-24 awg (1.5-0.2mm
2
).
Strip Length
—
0
.31” (8mm).
SCREW TERMINALS:
Solid/Stranded wire
—
14-28 awg (2.1-0.08mm
2
).
Strip Length
—0.24” –
0.28 (6-7mm).
Torque Rating
—
2 in-lbs (0.2 N-m).
8.9
Analog Outputs
NOTE:
Refer to the datasheet for EXL10/XL10 PRIME OCS model being used for details on jumper settings.
The analog outputs on EXL10/XL10 PRIME OCS devices provide high resolution voltage or current outputs.
The voltage or current selection is controlled with jumpers and configuration settings in Cscape.
NOTE:
Each channel can be separately configured for voltage or current mode.
When the controller is stopped, the operation of each output is configurable. The outputs can hold the
state they were in before the controller stopped or they can go to a predetermined value. By default,
analog outputs are set to a value of zero. For more information on Stop State, refer to the appropriate
pages (see
) for the configuration chapter for Cscape settings.