background image

Page

24VF Gas Fireplace

Part No. XG0138

Horizon 

Installation

When installing a shelf over the top of  the fireplace, the following 

guidelines must be adhered to:  The minimum clearance from the top 

of the fireplace to a shelf is 8 cm.

Figure 3.  

Framing for shelves over the fireplace.

Figure 2.  

Framing dimensions.

* When sheetrock is 
not used behind the 
fireplace, framing 
depth may be reduced 
to 18 cm

Framing

WARNING:

When this appliance is installed directly on carpeting, tile or 

any combustible material other than wood flooring, it must 

be installed on a metal or wood panel extending the full 

width and depth of the appliance.

Clearances

These clearances apply to all dimensions 

except the framed opening

where the clearance to combustibles is 

0 cm

. The 

24VF 

clearances to 

combustible materials are:

 

Top 

8 cm

 

Back 

0 cm 

 

Sides 

0 cm

 

Floor 

0 cm

 

Mantle** 

31 cm

*  Clearance from the top of the fireplace to a combusti

-

ble ceiling within the fireplace enclosure.

**  Refer to page 5.

Unprotected combustible walls which are perpendicular to the fire

-

place opening, must fall within the limits outlined in Figure 7.
For protection against freezing temperatures, it is recommended that 

outer walls of the chase be insulated with a vapour barrier. This will 

reduce the possibility of a cold-air convection current on the fireplace.

Space Requirements

This heater must not be installed in a confined space or unusually 

tight construction unless provisions are made for adequate combus

-

tion and ventilation air.
The National Fuel Gas Code, ANSI Z223.1, defines a confined space 

as a space whose volume is less than 50 cubic feet per 1,000 BTU 

per hour (4.8 m

3

 per kw) of the aggregate input rating of all appliances 

installed in that space and an unconfined space as a space whose 

volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8 m

3

 

per kw)  of the aggregate input rating of all appliances installed in that 

space. Rooms communicating directly with the space in which all the 

appliances are installed, through openings not furnished with doors, 

are considered a part of the unconfined space.

Example:

If you are installing this fireplace in a rectangular room which meas

-

ures 12' × 15' × 8' in height, that room will have a volume of 1440 cu. 

ft. (ft

3

).  If there is no other appliances in the room which consume 

oxygen, then the maximum BTU fireplace which can be installed in 

such a room is  28,800 BTU (1440 ft

3

 ÷ 50 × 1000) 

The minimum 

volume of space in which this fireplace can be installed is  equal 

to:

18,000 BTU's / hour ÷ 1000 = 18 kBTU/h

 

18 kBTU/h × 50 ft

3

 / kBTU/h =  900 ft

Therefore this heater may be installed in the space 

 

Figure 4. 

Dimensions of the room example.

Содержание 24VF

Страница 1: ...ire or explosion may result causing propertydamage personalinjury or loss of life F o r Y o u r Safety Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combus tion and ventilation air must be provided Refer to page 3...

Страница 2: ... are in the same room as the appliance Clothing or other flammable materials should not be placed on or near the appliance Any safety screen or guard removed for servicing an ap pliance must be replaced prior to operating the heater Installationandrepairshouldbedonebyaqualifiedservice person The appliance should be inspected before use and at least annually by a professional service person Morefre...

Страница 3: ... barrier This will reduce the possibility of a cold air convection current on the fireplace Space Requirements This heater must not be installed in a confined space or unusually tight construction unless provisions are made for adequate combus tion and ventilation air The National Fuel Gas Code ANSI Z223 1 defines a confined space as a space whose volume is less than 50 cubic feet per 1 000 BTU pe...

Страница 4: ...valve pressure measuring port If leaks are determined then repair and repeat the pressure test procedure 5 Turn main gas control pilot knob OFF during any pressure testing Test pressure should be equal to or less than 3 5 kPa to prevent dam age to control valve 6 Installation requirements and combustion and ventilation air provi sions must conform with local codes 7 Keep the operating area clear a...

Страница 5: ...Y WAY to do so restricts the air supply for the control compartments and it also prevents access for servic ing controls The face of the fireplace may be painted to match the room decor provided you use a heat resistant paint Decorative facing must not extend past the fireplace opening at all because it will interfere with the access to retainers for removal of screen door Figure 6 Combustible man...

Страница 6: ...lling the Logset Installing the Logs The 24VF is supplied with a two piece fibre logset The logset is very fragile and must be handled very carefully 1 Remove the screen door as shown in figure 8a 2 To install the logs place the rear log in place on the rear log rest Ensure that the log is centered in place as shown below Place the front log in place on the front logrest and center it in place 3 R...

Страница 7: ...m then the room is an unconfined space and qualifies for unvented heater installation If the result is less than the accumulated BTU of all the appliances in the room then the room is a confined space and the unvented heater should not be installed in such a small room This heater shall not be installed in a room with unusually tight construction as defined as follows Walls and ceilings exposed to...

Страница 8: ... supplier call the Fire De To Turn Off Gas To Appliance Operating Instructions 1 Flip down the lower grill 2 Push in gas control knob slightly and turn clockwise to Off Do not force 3 Flip up the lower grill 1 STOP Read the safety information above on this label 2 Flip down the lower grill 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas...

Страница 9: ...ce if any part has been under water Imme diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions Lighting Instructions See page 8 Burner Adjustment The 24VF is equipped with an adjustable burner allowing you to raise or lower the flames 1 Light the pilot as per the light...

Страница 10: ...rs This is available at hardware and computer stores and is sometimes labelled as a duster Do NOT use an air compressor as the air from a compressor usually contains oil The correct product usu ally has a small straw that connects to the can to aim the air Cleaning the ODS Sensor Must be performed by a certified gas technician 1 Locate the pilot assembly on your stove 2 Turn on the gas valve on th...

Страница 11: ...ce these parts CORRECTIVE ACTION Push the knob in at PILOT position and spark piezo ignitor for at least 10 seconds If pilot does not light repeat 2 or 3 more times If pilot still does not light call a certified technician Bleed air from line eliminate draft make sure gas is going to pilot Ventilate room and let stove burn for a while Ventilate room and stop using odor causing products while stove...

Страница 12: ...Page 12 24VF Gas Fireplace Part No XG0138 Horizon Notes ...

Страница 13: ...manufactured or supplied by Montigo DelRay Corp 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and unde...

Страница 14: ...Canadian Heating Products 27342 Gloucester Way Langley BC XG0138 122006 Installed and Serviced by Horizon ...

Отзывы: