Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

5

68-0282—07

Installing fresh air damper, ducting, 
and control…

1.

Disconnect power from HVAC system. 

2.

Install the weather hood, ducting, and damper following 

local practices. Be sure all duct and insulation seams 

are tightly sealed.

3.

Mount the transformer and control.

TIPS:

• In general, larger ducting allows higher airflow, minimizes 

additional fan run time and may be needed for larger 

homes.

• Installing a damper directly to the return duct may be 

convenient to support the damper and reduce ducting.

• Fresh air connection should be downstream of sensors 

(such as a humidistat) in return air plenum.

• The EARD6 end stops can be used to reduce the amount 

of airflow in the duct. To prevent complete opening, loosen 

(but do not remove) the wing nut and move the upper lever 

until the desired position is reached. Tighten the wing nut. 

Keep the lower lever in the position shown.

Wiring the control…

CAUTION

Electrical Hazard.

Can cause personal injury or equipment damage.

Disconnect power to all systems before beginning 

installation.

1.

Wire the control. See wiring diagrams in Fig. 1-10 as 

listed below. All wiring must comply with local codes, 

ordinances, and regulations.

2.

Reapply power to system and control.

TIP:

• Control package allows wire routing through side slots and 

bottom openings. 

UPPER LEVER

WING NUT

LOWER LEVER

M20155

System Hookup Diagrams

Fig. No.

Page No.

Single transformer, conventional 

1

10

Dual transformer, conventional

2

10

Multi-stage, conventional

3

10

Heat pump without emergency heat

4

10

Heat pump with emergency heat

5

11

Accessory Hookup Diagrams

Fig. No. Page No.

Wiring with a PC8900 Thermostat

6

11

Wiring with a remote switch/timer

7

11

Wiring to an HRV/ERV

8

11

Wiring an exhaust fan

9

11

Wiring a fan for a steam humidifier

10

12

Содержание Y8150

Страница 1: ...luding ASHRAE 62 2 2010 standard Ventilation and Acceptable Indoor Air Quality in Low Rise Residential Buildings Microcontroller optimizes the air delivery schedule to make efficient use of normal HVAC run times Easy to use input dials allow customized ventilation for each installation Test mode that includes immediate feedback to installer to confirm that air delivery requirements of selected ven...

Страница 2: ...6 24 Vac 12 VA 60 Hz Operation Power open spring closed Diameter 6 in Transformer AT120 Input 120 Vac Output 27 Vac open circuit 24 Vac full load at 20 VA Mounting Foot mounted Temperature 20 F to 160 F 29 C to 71 C Humidity 5 to 90 RH noncondensing Input Setting Ranges Bedrooms 2 5 Area 1000 4600 sq ft Vent Airflow 40 160 cfm Composite Setting Resolution 12 of ASHRAE 62 2 2010 recommended ventila...

Страница 3: ...entilation continuously Off Remote Only W8150 supplies ventilation only when there is a remote call 8 Light Green Indicates device is powered and operating normally Used in Test Mode to signal if dial settings meet chosen standard 9 Light Red Indicates the device is not operating normally Used in Test Mode to signal if dial settings do not meet chosen standard 10 DIP1 Ventilation limit Choose betw...

Страница 4: ...inals 24 Vac dry contacts allow W8150 to control an auxiliary device such as exhaust fan or HRV ERV with a call for ventilation 18 DAMPER Damper two terminals 24 Vac powered contacts control fresh air damper 19 XFMR C 24 Vac ventilation control common Supplies power to W8150 and damper from transformer provided 20 XFMR R 24 Vac ventilation control power Supplies power to W8150 and damper from tran...

Страница 5: ...ut and move the upper lever until the desired position is reached Tighten the wing nut Keep the lower lever in the position shown Wiring the control CAUTION Electrical Hazard Can cause personal injury or equipment damage Disconnect power to all systems before beginning installation 1 Wire the control See wiring diagrams in Fig 1 10 as listed below All wiring must comply with local codes ordinances...

Страница 6: ... the control to meet the ventilation requirements for the home Ventilation Standard Building codes are different everywhere The W8150 Ventilation Control can be configured to operate based on ASHRAE 62 2 ASHRAE 62 1999 TIP Clear understanding of local codes and practices is required to make sure the ventilation system is installed and configured correctly Generally ASHRAE 62 2 control method is re...

Страница 7: ...area sq ft dial to the nearest value For airflow set airflow cfm dial to the nearest value Vaulted ceilings do not need to be considered when setting this control For homes with multiple systems Honeywell recommends a ventilation control and fresh air intake for each system Measure ventilation airflow for each system independently Refer to Multi system Setup Example for further details Customizing...

Страница 8: ...blem Not enough airflow Ventilation on time limit setting If the device is set to 60 Set the ventilation control to 100 maximum on time This allows the HVAC fan to run up to 100 of the time It may be preferable to increase airflow If the device is set to 100 There is not enough airflow through the fresh air duct Ventilation continues to occur according to the settings but chosen standard may not b...

Страница 9: ...ed to actuator Damper actuator motor failure or mechanical failure Manually open damper and verify free movement damper should return to closed position when no power is applied If damper moves freely but does not operate when 24 volts is applied replace damper actuator If damper does not move freely replace fresh air damper Cooling compressor comes on when there is no cooling call from the thermo...

Страница 10: ...mp without emergency heat Wake Room System Fan Heat Auto AM DST Tue R C W Y G R RC W Y G M19994A GF RC CC CH W GT W8150A HVAC Wake Room System Fan Heat Auto AM DST Tue W R HVAC COOLING HEATING R C C Y G R RC W Y G M19995A GF RC CC CH W GT NOTE REMOVE FACTORY INSTALLED JUMPER BETWEEN CC AND CH ON W8150 W8150A Wake Room System Fan Heat Auto AM DST Tue W1 C R W2 Y1 Y2 G W1 C RC R W2 Y1 Y2 G M19996 GF...

Страница 11: ...TTON ON THE PC8900 THEN SERVES AS A REMOTE AND THE W8150 CONTROLS BACKGROUND VENTILATION Ventilation Control Ventilation Control Service Auto Continuous Off Remote Only M22000 EARD 6 FAN TIMER REMOTE AUX DAMPER C R XFMR AT120 W8150A Ventilation Control Ventilation Control Service Auto Continuous Off Remote Only M22001 HR150 ER150 EARD DAMPER NOT USED WITH HRV ERV REMOTE AUX DAMPER C R XFMR RED BLA...

Страница 12: ...red at 127 cfm System 2 serves 1800 sq ft four bedrooms fresh air intake measured at 98 cfm Set W8150 for System 1 3100 sq ft four bedrooms 130 cfm Set W8150 for System 2 1900 sq ft two bedrooms 100 cfm CONVERSION TABLE Wake Room System Fan Heat Auto AM DST Tue W1 C R W2 Y1 Y2 G W1 C RC R W2 Y1 Y2 G M22021A GF RC CC CH W GT HVAC W8150A HE440 FAN R8222 BLACK BLUE BLUE RED Area Airflow sq ft sq m cf...