FIGURE 3: CO GAS ENTRY LOCATION

  

CO

 

S0339-00

MAINTENANCE

The W4 detector reports maintenance issues to the control panel and com-
municates them visually and audibly per Table 2.

Trouble feature: When the sensor (supervision) is in a trouble condition (such 
as a detector that is dirty or CO sensor non-functioning), the detector will 
send a trouble signal to the panel. Depending on the issue, the detector must 
then be serviced or replaced.

CO sensor end-of-life timer feature: When the CO sensor has passed end-of-
life, a trouble signal will be sent to the panel. This indicates that the CO sensor 
inside the detector must be replaced. If unresolved for 30 days, the detector 
will chirp intermittently. The typical life of the CO sensor is ten years from the 
date of manufacture; it is recommended to periodically check the “Replace 
by” sticker located on the back of the detector head.

Batteries: WARNING: Use only Duracell DL123A or Panasonic CR123A lithium 
Batteries may present risk of fire or explosion. Remove all old batteries, wait 
10 seconds then insert four new batteries.

NOTE: Before performing any maintenance on the detector, notify the proper 
authorities that maintenance is being performed and the system will be tem-
porarily out of service. Disable the zone or system undergoing maintenance 
to prevent any unwanted alarms. Power must be removed from the detector 
before performing maintenance of any kind.

CLEANING

1.   Remove the detector head by turning counterclockwise.
2.   Clean the outside casing with a cloth. Ensure that the holes on the front 

of the alarm are not blocked with dirt and dust. Canned air can be used 
to remove any dust or debris.

3.   Reattach the detector head to the mounting base by rotating clockwise. 

FIGURE 2: TEST BUTTON LOCATION AND OPERATION

 

 

S0338-00

SMOKE ENTRY TEST / SMOKE SENSITIVITY READOUT

To smoke test W4, because it is a multi-criteria detector), it must be put into 
the smoke test mode as follows: 

1.   With the detector in standby mode, press and hold the smoke test button 

for 3 to 5 seconds. The W4 will provide diagnostic information including 
sensor status and smoke sensitivity reading and will prompt for smoke 
entry and annunciate per Table 2. 

2.   While W4 is in smoke entry mode with its green LED flashing, spray 

canned smoke into the detector. The canned smoke that can be used is 
approved for test include: Home Safeguard Industries 25S, SDi CHEK02 
and CHEK06, SDi SOLOA4, and SDi SMOKESABRE". 

3.   When the detector senses the presence of the smoke, the detector will 

sound and illuminate per Table 2 and a smoke alarm signal will be sent 
to the control panel with a test indication. 

4.   Verify the smoke alarm signal was received by the control panel.

FUNCTIONAL GAS TEST

Solo C6 brand canned CO may be used to verify the detector’s ability to sense 
CO by utilizing the RealTest® feature as follows:

1.   Press and hold the CO test button for 3 to 5 seconds. The green LED will 

start blinking rapidly indicating tshe detector is in RealTest® mode. (If the 
detector will not go into RealTest® mode, the CO sensor may be in fault 
or at end-of-life.)

2.   While the green LED is blinking rapidly, spray a small amount of canned 

CO directly into the CO gas entry port. (See Figure 3.)

3.   The detector will go into CO alarm and send an alarm to the channel 

panel if the gas entry was successful and the CO sensor is detected it-
functioning properly.

4.   Verify the smoke CO alarm signal was received by the control panel.
5.   The CO test will automatically clear when the CO clears from the sensor 

or in 30 seconds if no CO was introduced.

TABLE 2: LED INDICATION & SOUNDER DURING TEST AND MAINTENANCE

MODE

STATUS LED (TOP)

LED 

WINDOWS 

(SIDE)

SOUNDER

SPEAKER

Smoke Alarm System Test – Waiting for smoke entry 

(Press and hold Smoke test button 3-5 seconds)

Blink green  

once a second

Dark

Silent

Voice instructions for testing including warning of alarm 

signal

Smoke Alarm System Test (Upon successful smoke 

entry)

Blink red  

every 10 seconds

Blink red

Temp-3

Voice smoke warning

RealTest® Functional CO gas entry test - Waiting 

for gas entry (Press and hold CO test button 3-5 

seconds)

Blink green  

once a second

Dark

Silent

Voice instructions for testing including warning of alarm 

signal

RealTest

®

 Functional CO gas entry test -Upon 

successful gas entry

Blink red  

every 10 seconds Blink blue

Modified 

Temp-4

Voice carbon monoxide warning

Low Battery

Blink Amber  

every 45 sec

Dark

Chirp Every 

45 seconds 

after 7 days

Voice instructions by pressing either test button

Smoke Maintenance

Blink Amber  

every 5 seconds

Dark

Silent

Voice smoke maintenance instructions if Smoke test button 

is pressed

CO Trouble

Blink Amber  

every 5 seconds

Dark

Silent

Voice CO maintenance instructions if CO test button is 

pressed

CO End of Life - First 29 days

Blink Amber  

every 3 seconds

Dark

Silent

Voice end of life instructions if CO test button is pressed

CO End of Life - 30 days after panel notification

Blink Amber  

every 3 seconds

Dark

Chirp Every 

45 Seconds Voice end of life instructions if CO test button is pressed

  

I56-5942-000 

 

 09-14

Содержание W4-IC

Страница 1: ...ifferent battery may have a detrimental effect on device operation Number of Batteries 4 Sensitivity 0 9 to 2 64 ft 27 to 80 m Audible Signal 85dBA Physical Specifications Diameter 5 95 inches 15 113 cm Height 2 03 inches 5 1562cm Weight 13 92oz 383 g Operating Temperature Range 0 38 C 32 100 F Storage Temperature Range 10 70 C 14 158 F Operating Humidity Range 20 95 RH This product is compatible ...

Страница 2: ... Zone screen If all of the sensors have not been configured the Modify screen appears for each sensor to let you review its details Change the details as needed or tap Next to cycle through all sensors The sensors are marked as configured MOUNTING Physically mount the smoke detector in the desired location NOTE NFPA 72 recommends the installation of detectors only after complet ing construction or...

Страница 3: ...and SDi SMOKESABRE 3 When the detector senses the presence of the smoke the detector will sound and illuminate per Table 2 and a smoke alarm signal will be sent to the control panel with a test indication 4 Verify the smoke alarm signal was received by the control panel FUNCTIONAL GAS TEST Solo C6 brand canned CO may be used to verify the detector s ability to sense CO by utilizing the RealTest fe...

Страница 4: ...sistance Also young children elderly and pets may be the first to be affected CO ALARM ACTIVATION Per UL standard 2075 the W4 series detector has been tested to the sensitivity limits defined in UL standard 2034 TABLE 4 CO ALARM THRESHOLDS Parts per Million ppm Detector Response Time Min 30 3ppm No alarm within 30 days 70 5ppm 60 240 150 5ppm 10 50 400 10ppm 4 15 FCC STATEMENT This device complies...

Отзывы: