Honeywell VVT Скачать руководство пользователя страница 4

M6113

1

L1 
(HOT)

L2

5 R

C

4 W

6

Y

1

2

3

4

5

6

7

8

1

L1 
(HOT)

L2

5 R

C

4 W

6

Y

CW

(OPEN)

COM

CCW

(CLOSED)

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

VVO BD
DAMPER

CDO-52
VVA RD
DAMPER

VVT (T641A)

OR

VVT-HC (T641C)

Settings

TEMPERATURE SETTING

Move the heating and cooling set point levers to the

desired comfort positions. See Fig. 3.

SWITCH SETTING

The VVT-HT (T641C) has a manual heat/cool changeover

switch. With this switch set in the cool position, wire to
damper actuator as shown in Fig. 4. Be sure to determine
direction of damper opening for correct wiring between the
thermostat and the actuator. The changeover switch can be
placed in the heat position to reverse action at terminals 4 (W)
and 6 (Y).

Checkout

With the VVT (T641A) or VVT-HC (T641C) Thermostat

controlling the damper or equivalent actuator, lower the set
point of the thermostat to call for cooling. Observe the
operation of the motor. If the damper is closed, it should begin
to open. If not, adjust the set point of the thermostat higher to
determine if the wiring is correct. If no movement is ob-
served, check for the presence of 24 Vac between terminals
of the motor during a call for cooling. With the proper wiring
and 24 Vac present, the actuator should operate correctly. If
24 Vac is not present on a call for cooling, replace the
thermostat.

To check out the damper when controlled by the thermo-

stat, determine the direction the damper shaft moves to open
the damper. Place 24 Vac across the appropriate common and
open terminal to energize the actuator after disconnecting the
external wires. The damper should begin to open the damper.
If the motor does not run, try switching the 24 Vac across the
opposite terminals to determine if the damper will begin to
close. Replace the damper if the motor does not run in either
direction.

Fig. 4—Dampers used with VVT (T641A) and VVT-HC (T641C) Thermostats for Type B damper applications.
Y terminal energizes counterclockwise (ccw) winding on call for cooling, driving motor open.

HONEYWELL TROL-A-TEMP
57 BUSHES LANE  •  ELMWOOD PARK, NJ  07407-3204
TELEPHONE: 201-794-8004, 800-828-8367  •  FAX:  201-794-1359

PRINTED IN MEXICO

Содержание VVT

Страница 1: ... only in true VAV systems Pressure dependent systems do not incorporate an indi vidual zone air flow sensor and depend on a stable system pressure to maintain flow These systems require slower motorssuchasthesevenminutedampers whicharetypically controlled by the VVT T641A or VVT HC T641C Ther mostats HEAT ANTICIPATION COOL ANTICIPATION Controlofheatingorcoolingunitswithathermostatdoes notallowfort...

Страница 2: ...ercury switches See Fig 3 2 Run wiring from the actuator if necessary to the location If the wiring is plastered into the wall make a hole next to the cable and loosen the wires so they can be pushed backintothewalllater Threadwiresthroughholeinpacking materialsavedinstep1 Connectthewirestotheterminalson the back of the thermostat See Fig 4 3 Push the excess wire back through the hole and plug any...

Страница 3: ...AL SET POINT LEVER FRONT OF THERMOSTAT COVER REMOVED Y C X W R MOUNTING HOLES 4 BACK OF VVT T641A 4 C X 6 5 MOUNTING HOLES 4 BACK OF VVT HC T641C Fig 3 Mounting thermostat using accessory wallplate 80 70 60 50 WARM COOL HONEYWELL PART NO 221618 ACCESSORY WALLPLATE THERMOSTAT BASE MOUNTING SCREWS 4 THERMOSTAT COVER M6111 EXTERNAL SET POINT LEVER M6110 ...

Страница 4: ...en If not adjust the set point of the thermostat higher to determine if the wiring is correct If no movement is ob served check for the presence of 24 Vac between terminals ofthemotorduringacallforcooling Withtheproperwiring and 24 Vac present the actuator should operate correctly If 24 Vac is not present on a call for cooling replace the thermostat To check out the damper when controlled by the t...