Honeywell VT8800 Скачать руководство пользователя страница 9

VT8800/WT8800 WATER HEATER CONTROLS

9

69-1731

Fig. 8. Troubleshooting Without Status Light.

Thermopile Output Check.

1.

Turn device knob to OFF.

2.

Disconnect thermopile leads.

3.

Turn device knob to PILOT, hold down knob to light 
pilot burner.  Hold the knob down for five or more 
minutes.

4.

After five minutes, check thermopile output by 
connecting the voltmeter to the positive red lead 
and negative white leads.

5.

Output should be at least 350 mV. (See Fig. 8.)  
Connect the 3.6 ohm resistor between the two ther-
mopile leads, the voltage should be at or higher 
than one half of the open circuit voltage.

6.

The terminals prevent miswiring of positive (1/4 in.) 
and negative (3/16 in.) leadwires.

7.

Flame must envelop thermopile at Hot Junction 
(3/8 in. below tip).

8.

Keep heat away from cold junction (brass sleeve) 
for maximum output.

Fig. 9. Thermopile output.

Sensor Calibration Check

1.

Turn device knob to OFF.

2.

Disconnect sensor leads (1 x 4 connector).

3.

Use ohmmeter to check resistance on upper or 
lower sensor (see wiring diagram).

4.

Typical resistance values will be between 1700 
ohms (160°F tank temperature) and 9300 ohms 
(80°F tank temperature).

5.

Replace sensor assembly if you measure open 
circuit or the ohms reading is significantly out of 
range.

INSTRUCTIONS TO THE 

HOMEOWNER

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

1. 

IF YOU SMELL GAS:

    • Turn off the gas supply at the appliance

   service valve. On LP systems, turn off the 
   gas supply at the gas tank.

    • Do not light any appliances in the house.
    • Do not touch electrical switches or use the

   phone. Leave the building and use a
   neighbor’s phone to call your gas supplier.

    • If you cannot reach your gas supplier, call 

   the fire department.

2.

 The water heater control must be replaced in 

event of any physical damage, tampering, bent 
terminals, missing or broken parts, stripped 
threads or evidence of exposure to heat.

TURN DEVICE KNOB FROM OFF TO 

PILOT, PRESS DOWN KNOB AND HOLD, 

LIGHT PILOT BY DEPRESSING PIEZO 

IGNITION BUTTON, PILOT SHOULD 

LIGHT

CHECK:

• WIRING OF THERMOPILE LEADS

• FLAME COVERAGE OF THERMOPILE

• THERMOPILE OUTPUT IS TOO LOW-RUN  

 THERMOPILE OUTPUT CHECK

STATUS LIGHT SHOULD FLASH AFTER 

1 MINUTE, LED WILL FLASH NORMAL 

SINGLE BLINK, RELEASE THE DEVICE 

KNOB, PILOT SHOULD REMAIN LIT

TURN DEVICE KNOB TO DESIRED

TEMPERATURE SETTING, BURNER WILL

TURN ON ONLY IN ACTIVE CALL FOR

HEAT (WATER TEMPERATURE IS LESS 

THAN TEMPERATURE SETTING MINUS 

DIFFERENTIAL)

SYSTEM OK

CHECK:

• EXCESSIVE INLET PRESSURE

• TANK TEMPERATURE IS AT OR CLOSE

  TO SET POINT.

• RUN SENSOR CALIBRATION CHECK

NO

NO

NO

YES

YES

YES

M22536C

TROUBLESHOOTING GUIDE WITHOUT STATUS LIGHT

CHECK:

• INLET PRESSURE

• MAKE SURE AIR IS BLED OUT OF SYSTEM

• PIEZO SPARKING TO THERMOPILE

• CLOGGED PILOT ORIFICE

• GAS LEAK IN PILOT TUBING CONNECTIONS

M22535B

TIME (MINUTES)

OUTPUT (mV)

THERMOPILE OUTPUT WITH TIME

500

600

400
300
200
100

0

0

1

2

3

4

5

6

7

8

9

10

900
800
700

NORMAL RANGE

OUTPUT TOO LOW

69-1731.fm  Page 9  Monday, October 10, 2005  11:02 AM

Содержание VT8800

Страница 1: ...tlet Mounting Mounting in upright position only Control Input Voltage Minimum 350 mV dc open circuit Voltage Maximum 850 mV dc open circuit Capacity See Table 1 Conversion Use conversion factors in Table 2 to convert capacities for other gases Regulation Range VT8800 with 1 2 in NPT inlet and 1 2 in Inverted Flare Outlet Natural Gas Minimum 30 000 Btuh Maximum 85 000 Btuh LP Gas Minimum 40 000 Btu...

Страница 2: ... fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check out the system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the control Where chemicals are suspended in air as in some industrial or agricul...

Страница 3: ...ained when the appliance is installed INSTALLATION When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation ...

Страница 4: ...flare outlet facing down Secure valve using one screw two piece design 5 Install WT8800 control electronics on the three pins of the gas valve and snap into place Secure with one screw 6 Be certain to mount the VT8800 WT8800 so that the gas flow is in the direction of the arrow on the inlet side of the control 7 Follow steps in Connect Gas Supply section which follows IMPORTANT These water heater ...

Страница 5: ...e only ANSI approved compounds Wiring Follow the wiring instructions furnished by the appliance manufacturer if available or use the general instructions provided below When these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions Make sure wiring insulation does not get cut by sharp edges NOTE All wiring must comply with applicable electrical codes ...

Страница 6: ...temperature at the setpoint knob WARNING Scalding Hazard Can cause burns severe injury or death Never move setpoint knob past the Hot setting unless extremely hot water is desired Always check water temperature at the faucet and readjust until comfortably warm to the touch Consider the ages and health of all who will come in contact with heated water Perform Gas Leak Test WARNING Fire or Explosion...

Страница 7: ...etermined individually for each application Some considerations are 1 Cycling frequency Appliances that may cycle 10 000 times annually should be checked monthly 2 Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use 3 Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checke...

Страница 8: ... available Inspect thermopile connection to valve flame coverage on thermopile inspect orifice assembly for dirt check inlet pressure run open circuit thermopile output test and change thermopile if output is low 3 flashes Sensor or Valve failure Pilot On Main Valve Off Restart control If main turns on after restart replace sensor If main does not turn on after restart replace valve 4 flashes Valv...

Страница 9: ...gas supply at the appliance service valve On LP systems turn off the gas supply at the gas tank Do not light any appliances in the house Do not touch electrical switches or use the phone Leave the building and use a neighbor s phone to call your gas supplier If you cannot reach your gas supplier call the fire department 2 The water heater control must be replaced in event of any physical damage ta...

Страница 10: ...tructions 1 Set the temperature setpoint knob to OFF 2 Turn off the main gas valve to the appliance 3 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow step 1 in the warning above If you DO NOT smell gas continue with the next step 4 Turn on the main gas valve to the appliance 5 Replace the water heater control access panel if provided 6 Restart the appliance by per...

Страница 11: ...11 69 1731 69 1731 fm Page 11 Monday October 10 2005 11 02 AM ...

Страница 12: ...l Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 69 1731 S A 10 05 69 1731 fm Page 12 Monday October 10 2005 11 02 AM ...

Отзывы: