Dust or Grease Accumulation

Heavy accumulations of dust or grease can cause the 

control to malfunction. Where dust or grease can be a 

problem, provide covers for the control to limit 

contamination.

Heat

Excessively high temperatures can damage the control. 

Make sure the maximum ambient temperature at the 

control does not exceed the rating of the control. If the 

appliance operates at very high temperatures, use 

insulation, shielding, and air circulation, as necessary, to 

protect the control. Proper insulation or shielding should 

be provided by the appliance manufacturer; verify proper 

air circulation is maintained when the appliance is 

installed.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a 

hazardous condition.

2.

Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury 

or death.

Follow these warnings exactly:

1. Disconnect power supply before wiring to 

prevent electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas, 

turn off gas supply at the appliance service 

valve before starting installation, and perform 

Gas Leak Test after installation is complete.

3. Always install a sediment trap in gas supply line 

to prevent contamination of gas control.

4. Do not force the on-off switch. Use only your 

fingers to operate the on-off switch. Never use 

any tools. If the electronic on-off switch does 

not operate by hand, the gas control should be 

replaced by a qualified service technician. 

Force or attempted repair may result in fire or 

explosion.

5. Gas will leak if installed backwards.

CAUTION

Equipment Damage Hazard.

Can burn out thermostat or transformer.

Applying a jumper across (or shorting) the valve 

coil terminals, even temporarily, can burn out the 

thermostat or transformer.

Follow the appliance manufacturers instructions if 

available; otherwise use these instructions as a guide.

IMPORTANT

These gas controls are shipped with protective 

seals over the inlet and outlet tappings. Do not 

remove the seals until ready to install adapters 

or connect the piping.

Converting Gas Control from 

Natural Gas to LP Gas (or LP Gas 

to Natural Gas)

WARNING

Fire Or Explosion Hazard.

Can cause property damage, severe injury 

or death.

1. Always change the main orifices when 

converting from natural to LP gas or from LP to 

natural gas. Carefully follow appliance 

manufacturer specifications and instructions to 

assure proper appliance conversion.

2. Gas controls are factory-set for natural (and 

manufactured) or LP gas. Do not attempt to use 

a gas control set for natural (manufactured) gas 

on LP gas, or a gas control set for LP gas on 

natural (manufactured) gas.

Controls with standard and slow-opening regulators 

(model numbers with suffix S or T) can be converted from 

one gas to the other with a conversion kit. See Table 4 for 

the conversion kit part number.

1.

Turn off gas supply at the appliance service valve.

2.

Remove regulator cap screw and save. See Fig. 5.

3.

Remove the pressure regulator adjusting screw. 

See Fig. 1.

4.

Remove the existing spring.

5.

Insert the replacement spring. See Fig. 1.

6.

Install the new plastic pressure regulator adjust-

ment screw.

7.

Check the regulator setting using a manometer or 

by clocking the gas meter. See “Check and Adjust 

Gas Input and Burner Ignition” on page 6.

8.

Reinstall the regulator cap screw.

9.

Mount conversion label on the gas control.

Fig. 1. Converting between LP and natural gas.

COLOR CODE FOR

LP
GAS

NATURAL
GAS

PRESSURE

REGULATOR

ADJUSTING

SCREW

BLACK

BLACK

SPRING 

RED

STAINLESS
STEEL

PRESSURE
REGULATOR
HOUSING

M20046B

        

REUSE EXISTING METAL CAP SCREW.

1

1

Содержание VR8215S

Страница 1: ...IFICATIONS Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw 0 5A Field Wiring 2 1 4 in spade quick connect terminals Capacity See Table 1 Conversion Use conversion factors in Table 2 to convert capacities for other gases Regulation Range See Table 7 Natural LP Gas Conversion Kits See Table 4 Approvals CSA Desi...

Страница 2: ...et wet during normal cleaning procedures High Humidity or Dripping Water Dripping water can cause the control to fail Never install an appliance where water can drip on the control In addition high ambient humidity can cause the control to corrode and fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check...

Страница 3: ...r attempted repair may result in fire or explosion 5 Gas will leak if installed backwards CAUTION Equipment Damage Hazard Can burn out thermostat or transformer Applying a jumper across or shorting the valve coil terminals even temporarily can burn out the thermostat or transformer Follow the appliance manufacturers instructions if available otherwise use these instructions as a guide IMPORTANT Th...

Страница 4: ...ed standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing is used obtain a tube to pipe coupling to connect the tubing to the control 3 Install a sediment trap in the supply line to the control See Fig 3 Ins...

Страница 5: ... volt control in S89 Direct Ignition System STARTUP AND CHECKOUT On Off Switch The on off switch settings are as follows OFF Prevents main gas flow through the control M27669 M27670A ON OFF PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW INLET INLET PRESSURE TAP 1 8 IN NPT OUTLET ON OFF SWITCH OUTLET PRESSURE TAP 1 8 IN NPT 24V 24V GND S87B CONTROL MODULE ALARM VALVE VALVE GND TEMPERATURE CONTROLLER...

Страница 6: ...eing checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the gas control is in the OFF position before removing outlet pressure tap plug to connect m...

Страница 7: ...embly repair or cleaning can damage the control resulting in gas leakage Regular preventive maintenance is important in applications in the commercial cooking and agricultural and industrial industries that place a heavy load on system controls because In many such applications particularly commercial cooking the equipment operates 100 000 to 200 000 cycles per year Such heavy cycling can wear out...

Страница 8: ...e heating appliance manufacturer The information below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the ...

Страница 9: ...VR8215S T TRADELINE DIRECT IGNITION COMBINATION GAS CONTROLS 9 34 00006EF 01 ...

Страница 10: ...AS CONTROLS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2014 Honeywell International Inc 34 00006EF 01 M S 11 14 Printed in United States ...

Страница 11: ...éro de modèle CARACTÉRISTIQUES Configuration du corps Passage direct voir le Tableau 1 pour la taille d entrée et de sortie Caractéristiques électriques Tension et fréquence 24 V c a 50 60 Hz Appel de courant 0 5 A Câblage sur site Bornes rapides à cosse de po 6 mm Capacité Voir le Tableau 1 Conversion Utiliser les facteurs de conversion du Tableau 2 pour convertir les capacités pour d autres gaz ...

Страница 12: ...les n ont lieu que trois ou quatre fois par heure durant la saison de chauffage Pour les applications sur l année entière avec des cadences plus importantes le régulateur peut s user plus rapidement Effectuer une vérification mensuelle Nettoyage à l eau ou à la vapeur Si le régulateur se mouille le remplacer Si l appareil est susceptible d être lavé à l eau ou à la vapeur protéger couvrir le régul...

Страница 13: ...ou d explosion Peut causer des dégâts et des blessures graves voire mortelles Respecter ces avertissements avec précision 1 Débrancher l alimentation avant le câblage pour éviter les chocs électriques et les dégâts de l équipement 2 Pour éviter une accumulation dangereuse de gaz combustible couper l alimentation au niveau de la vanne de service de l appareil avant de commencer l installation et ef...

Страница 14: ...uivre ces instructions Placer le régulateur de gaz dans une zone bien ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l ea...

Страница 15: ...s dégâts de l équipement 1 Vérifier la tension électrique du régulateur et s assurer qu elle correspond à l alimentation disponible Installer un transformateur et d autres dispositifs si nécessaire 2 Brancher le circuit du régulateur sur les bornes du régulateur Voir les Fig 6 et 7 3 Régler l anticipateur de chaleur du thermostat à 0 50 A la valeur indiquée sur l opérateur de la vanne Dimension de...

Страница 16: ...achées qui pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé badigeonner les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur avec une solution savonneuse épaisse 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas...

Страница 17: ...ction de la pression nominale de l appareil Voir le Tableau 7 pour la pression de sortie nominale réglée en usine et la plage de réglage a Retirer la vis d obturation de réglage du régulateur de pression b Avec un tournevis tourner la vis de réglage interne de pression élevée Fig 5 dans le sens des aiguilles d une montre pour l augmenter ou dans le sens contraire des aiguilles d une montre pour ré...

Страница 18: ... dans la documentation du fabricant de l appareil La fréquence de l entretien doit être déterminée pour chaque application sur une basse individuelle Voici quelques considérations à prendre en compte Fréquence des cycles Les appareils dont les cycles peuvent avoir lieu 20 000 fois par an doivent être vérifiés mensuellement Utilisation intermittente Les appareils utilisés de manière saisonnière doi...

Страница 19: ...uvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche ARRÊTER Lire les avertissements avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pas tenter d allumer le brûleur prin cipal manuellement 2 Si l appareil de chauffage ne s allume pas lorsque le thermostat est réglé à plusieurs degrés au dessus de la température de la pièce régler le ...

Страница 20: ... de régulation et d automatisation Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com Marque de commerce déposée aux États Unis 2014 Honeywell International Inc Tous droits réservés 34 00006EF 01 M S 11 14 Imprimé aux États Unis ...

Отзывы: