VR8215S,T SINGLE STAGE VR8215Q,N TWO STAGE DIRECT IGNITION GAS CONTROLS
9
69-2253—07
Two Stage
To convert from one gas to another:
1.
Turn off gas supply at the appliance service
valve.
2.
Remove/unsnap plastic regulator cap. See
Fig. 8.
3.
Remove regulator assembly by rotating 7/16
Hex to left with supplied conversion tool. See
Fig. 9.
4.
Remove spring from regulator assembly and
replace with new spring.
5.
Reinstall regulator assembly back into valve
housing, turning clockwise with 7/16 Hex
conversion tool.
6.
Rotate regulator assembly 6 turns to reach a
nominal high fire setting of approximately
3.5 inches WC.
7.
Check the regulator setting using a manometer
or by clocking the gas meter. See “Check and
Adjust Gas Input and Burner Ignition” on page 5.
8.
Adjust high fire first by adjusting exterior 7/16
Hex, After high fire has been set, adjust low fire
utilizing interior 3/32 allen. See Fig. 8 and the
Two Stage Regulator Adjustment process, below.
9.
Reinstall the plastic regulator cap.
10.
Mount conversion label on the gas control.
11.
Install the gas control and appliance according
to the appliance manufacturer instructions.
Fig. 8. Top view of VR8215 two stage control with regulator cover removed.
C
HI
MV
ON
OFF
SET
SET
HI
LO SECOND
FIRST
HI
LO
INLET
OUTLET
PRESSURE REGULATOR
HIGH FIRE ADJUSTMENT
7/16 HEX
PRESSURE REGULATOR
LOW FIRE ADJUSTMENT
3/32 ALLEN
INLET
PRESSURE
TAP
REGULATOR CAP
COVER
ON/OFF
SWITCH
OUTLET
PRESSURE
TAP
ELECTRIC
CONNECTION
MOLEX OR
SPADE
M36774